Particle Swarm Optimization and Bacterial Foraging Optimization Techniques for Optimal Current Harmonic Mitigation by Employing Active Power Filter

Table 2

APF response comparison under ideal supply condition.

Case under considerationMaximum overshoot ( ) in volts transient settling time ( ) in sec.Source current THD in %

Without APFā€”ā€”20.61
APF with conventional PI96.50.0531.95
APF with PSO-PI53.20.0291.55
APF with BFO-PI118.90.0181.05