Behavior of Concrete Columns Repaired with Polymer Mortar and Epoxy Fiber Panel
Table 1
Variables of test columns.
| No. | Columns | Cut-out preparation | Form | Damage | Curing condition | Remarks |
| 1 | M1 | M series (Control) |
No cutout |
* |
* | | | 2 | M2 | | No repair | 3 | G-D-D1-1 | | Cast | | | | | 4 | G-D-D1-2 | G-D-D series | Chipping |
Acrylic plate | Damage1 | | | 5 | G-D-D2-1 | Cast | | Air | | 6 | G-D-D2-2 | | Chipping | | Damage2 | | | 7 | G-D-F-D1-1 | | | | | | | 8 | G-D-F-D1-2 | G-D-F-D series | | | Damage1 | | | 9 | G-D-F-D2-1 | | | | | | 10 | G-D-F-D2-2 | | | | Damage2 | | | 11 | U-W-F-D1-1 | | | | | | | 12 | U-W-F-D1-2 | U-W-F-D series | | | Damage1 | | | 13 | U-W-F-D2-1 | | Epoxy fiber panel | | | Repair with repair materials after removal of damaged concrete | 14 | U-W-F-D2-2 | | Chipping | | Damage2 | | | 15 | U-D-F-D1-1 | | | | | | | 16 | U-D-F-D1-2 | U-D-F-D series | | | Damage1 | | | 17 | U-D-F-D2-1 | | | | Underwater | | 18 | U-D-F-D2-2 | | | | Damage2 | | | 19 | U-D,S-F-D1-1 | | | | | | | 20 | U-D,S-F-D1-2 | U-D,S-F-D series | | | Damage1 | | | 21 | U-D,S-F-D2-1 | | Epoxy fiber panel/shear connector | | | | 22 | U-D,S-F-D2-2 | | | | Damage2 | | |
|
|
G: ground, U: underwater, D: dry, W: wet, S: shear connector, F: form (epoxy fiber panel), D1: damage1 (depth 5 cm), D2: damage2 (depth 7 cm), and 1/2: serial number.
|