External Thermal Insulation Composite Systems: Critical Parameters for Surface Hygrothermal Behaviour

Table 5

Relevance of the parameter values and expected variations in terms of surface condensation ( ), WDR, and drying process ( ).

ParameterInitial situationVariationRelevance
C WDRD

Properties of the exterior layer
 Moisture diffusivity, in (m2/s)00.0013*###
 Water vapour diffusion resistance factor251000###
 Emissivity (Figure 11)0.850.60#####
 Absorbance to solar radiation (Figure 12)0.350.50####
 Thickness, in (m)0.0050.02###
Characteristics of the façade
 Orientation (Figure 13)WN; E; S#####
 Height of the building (Figure 14)TallSmall#####
 Total thermal resistance (Figure 15) = 0.04 m = 0.06 m####
Exterior climate
 Temperature, in (°C) (Figure 16) #####
 Relative humidity, in (%) (Figure 17) #####
 Solar radiation, in (W/m2) (Figure 18) ####
 Atmospheric radiation, in (W/m2) (Figure 19) #####
 Wind velocity, in (m/s) (Figure 20) ####
 Wind direction, in (°) ####
 Rain, in (mm) (Figure 21)RainPorto0.20 × RainPorto#####
Interior climate
 Temperature, in (°C) (Figure 22)2022####
 Relative humidity, in (%)6065###

For moisture content at 80% of RH (WUFI database).
Scale: #Low. ##Medium. ###High.