[Retracted] Case Study of Carbon Emissions from a Building’s Life Cycle Based on BIM and Ecotect

Table 8

The sensitivity analysis of annual CO2 emissions by altering design configurations.

Design IDChanged to original designAnnual CO2 emission (t)Compared with D0Decreased

D0Existing design1463.92

D1Changing thermal transmittance coefficient, W/(m2·K)
(1) Exterior walls changed from 1.081 to 0.7131361.450.930.07
(2) Roof changed from 0.812 to 0.51452.210.9920.008
(3) Exterior windows changed from 5.700 to 2.1001346.810.920.08

D2Reducing the fresh air volume from 30 to 20 (unit, m3/(h·p))1258.970.860.14

D3Using nighttime ventilation
(1) Duration: June 1–September 30
Frequency of ventilation and air exchange: 2 times/h from 21:00 to 09:00 (the next morning); 0.5 times/h at all other times
1456.60.9950.005
(2) Duration: June 1–September 30
Frequency of ventilation and air exchange: 4 times/h from 21:00 to 09:00 (the next morning); 0.5 times/h at all other times
1452.210.9920.008

D4Extending the indoor temperature range from 18°C–26°C to 17°C–27°C1317.530.900.10