Research Article
Mitigation of Voltage Dip and Voltage Flickering by Multilevel D-STATCOM
Table 1
Performance comparison between the six-pulse and the five-level diode-clamped inverters.
| Type of inverter | D-STATCOM status | T.H.D. of | Voltage flickering | Voltage dip |
| Five-level diode-clamped inverter | Off | 12.16% | 2.09% | 17.50% | On | 0.29% | 0.00005% | Six-pulse inverter | Off | 36.35% | 2.09% | 17.50% | On | 0.68% | 3.043% |
|
|