Research Article

Fuzzy Inference System Approach for Locating Series, Shunt, and Simultaneous Series-Shunt Faults in Double Circuit Transmission Lines

Table 1

Test results of series faults location estimation.

Fault typeFault inception angle (°)Fault location (km)Estimated location (km)Error (%)

A1067.000−0.0045
B2453635.0000.0045
C1906666.0000.0000
A2B21359696.0000.0000
B1C1180126126.0000.0000
C2A2225156157.000−0.0045
A1B1C1270186189.000−0.0136