Fuzzy Inference System Approach for Locating Series, Shunt, and Simultaneous Series-Shunt Faults in Double Circuit Transmission Lines

Table 2

Test results of shunt faults location estimation.

Fault typeFault inception angle (°)Fault location (km)Estimated location (km)Error (%)

A1G099.0000.0000
B2G452927.0000.0090
C1G904949.665−0.0030
A2B2G1356970.200−0.0050
B1C1G1808988.6400.0010
C2A2G225109109.200−0.0009
A1B1270129132.600−0.0163
B2C2315149148.2000.0036
C1A10169171.200−0.0100
A2B2C290189195.000−0.0272