Conference Paper

Comparative Assessment of an Innovative Dry-Cooled CSP System

Table 3

Input data and scenarios for ST-CSP technology comparative analysis.

ScenarioCapacitySpecific capital costEfficiencyFixed O and MVariable O and MCapacity factor
MWe€/kW%€/kW/month€/MWh%

ST-CSP, water cooling, high DNI17647116.089.202.4822.40
ST-CSP, water cooling, normal DNI17647116.089.202.4817.30
ST CSP, water cooling, low DNI17647116.089.202.4813.30
ST-CSP, dry cooling, high DNI17658714.869.202.4821.20
ST-CSP, dry cooling, normal DNI17658714.869.202.4816.60
ST-CSP, dry cooling, low DNI17658714.869.202.4812.70
ST-CSP, MACC cooling, high DNI, 14.5% efficiency17648214.509.232.4820.20
ST-CSP, MACC cooling, high DNI, 15.5% efficiency17648215.509.232.4821.59
ST-CSP, MACC cooling, high DNI, 16.5% efficiency17648216.509.232.4822.99
ST-CSP, MACC cooling, normal DNI, 14.5% efficiency17648214.509.232.4815.60
ST-CSP, MACC cooling, normal DNI, 15.5% efficiency17648215.509.232.4816.68
ST-CSP, MACC cooling, normal DNI, 16.5% efficiency17648216.509.232.4817.75
ST-CSP, MACC cooling, low DNI, 14.5% efficiency17648214.509.232.4811.99
ST-CSP, MACC cooling, low DNI, 15.5% efficiency17648215.509.232.4812.82
ST-CSP, MACC cooling, low DNI, 16.5% efficiency17648216.509.232.4813.65