Performance Assessment of a Hybrid Solar-Geothermal Air Conditioning System for Residential Application: Energy, Exergy, and Sustainability Analysis
Table 1
Main assumptions for analysis (Isfahan case study, month of January).
| Parameter | Value |
| General parameters | | Design temperature | 22.5 (°C) | Dead state temperature | 10 (°C) | Ground temperature | 17 (°C) | Thermal load | 10.1 (kW) | Solar irradiance | 0.2 (kW m−2) | Battery efficiency | 70% | Power conversion efficiency | 18% |
| GSHX parameters | | Working fluid | Water | Inlet temperature | 5 (°C) | Outlet temperature | 15 (°C) | Soil resistance | 230 (kW−1 m °C) | Ground pump efficiency | 80% | Ground heat exchanger efficiency | 80% |
| Heat pump parameters | | Evaporator pressure | 200 (kPa) | Condenser pressure | 800 (kPa) | Refrigerant | R-134a | Condenser efficiency | 80% | Evaporator efficiency | 80% | Compressor efficiency | 80% | Expansion valve efficiency | 80% |
| Room heater parameters | | Working fluid | Water | Inlet temperature | 20 (°C) | Outlet temperature | 30 (°C) | Fan-coil heat exchanger efficiency | 80% | Fan-coil pump efficiency | 80% |
|
|