Effect of Neutral Grounding Protection Methods for Compensated Wind/PV Grid-Connected Hybrid Power Systems

Table 3

Minimization of fault currents at fault location X on the wind/PV GCS due to the SCF for different values of Peterson coil.

Fault inductance (Lf) (H)Maximum magnitude of fault current with the SCF (Amp)% change
Phase APhase BPhase C

15318615458100.36
104349573354207.73
3034575111488320.84
58.626984251398545.28
6524824069379951.78