Extraction of Transmission Parameters for Siting and Sizing of Distributed Energy Sources in Distribution Network
Table 3
Summarized results of both systems.
| Test systems | Methods | Optimal location | Optimal size (MVA) | Operating power factor | Type | Base active loss, kw (W/O DG) | Reduced active loss (kw) |
| 16-bus system | MTP | 9 | 13.634 | 0.88 | Type III | 515.4 | 190.4 | IA | 9 | 13.0877 | 0.98 | Type I | 511.43 | 164.02 | ELF | 9 | 13.1551 | 0.98 | Type I | 511.43 | 164.01 |
| 33-bus system | MTP | 6 | 3.2552 | 0.81 | Type III | 212.5 | 69 | IA | 6 | 3.0247 | 0.85 | Type I | 211.2 | 68.28 | ELF | 6 | 3.1034 | 0.85 | Type I | 211.2 | 68.2 |
|
|