Extraction of Transmission Parameters for Siting and Sizing of Distributed Energy Sources in Distribution Network

Table 3

Summarized results of both systems.

Test systemsMethodsOptimal locationOptimal size (MVA)Operating power factorTypeBase active loss, kw (W/O DG)Reduced active loss (kw)

16-bus systemMTP 913.6340.88Type III515.4190.4
IA 913.08770.98Type I511.43164.02
ELF 913.15510.98Type I511.43164.01

33-bus systemMTP 63.25520.81Type III212.569
IA 63.02470.85Type I211.268.28
ELF 63.10340.85Type I211.268.2