Research Article

Partial Least Squares (PLS) Integrated Fourier Transform Infrared (FTIR) Approach for Prediction of Moisture in Transformer Oil and Lubricating Oil

Table 8

The average % RMSE of prediction using partial least squares regression (PLSR) and simple linear regression (SLR) based on 100 training/test sets (concentration ranges 0–5000 ppm).

DataPrediction methodLubricating oil (%)Transformer oil (%)

TrainingPLSR14.1524.16
SLR14.8627.10

TestPLSR16.5528.63
SLR16.5330.95