Abstract

A mathematical model to compute the overall vibrational response of connected multistructure mechanical systems is presented. Using the proposed model, structural vibration control strategies for seismic protection of multibuilding systems can be efficiently designed. Particular attention is paid to the design of control configurations that combine passive interbuilding dampers with local feedback control systems implemented in the buildings. These hybrid active-passive control strategies possess the good properties of passive control systems and also have the high-performance characteristics of active control systems. Moreover, active-passive control configurations can be properly designed for multibuilding systems requiring different levels of seismic protection and are also remarkably robust against failures in the local feedback control systems. The application of the main ideas is illustrated by means of a three-building system, and numerical simulations are conducted to assess the performance of the proposed structural vibration control strategies.

1. Introduction

Over the last years, seismic protection of adjacent buildings has been attracting an increasing interest. For this kind of systems, the action of seismic excitations can produce interbuilding collisions (pounding), which can cause severe damage to the buildings structure and contents [15]. Consequently, structural vibration control (SVC) strategies for multibuilding systems must aim at mitigating not only the vibrational response of individual buildings, but also the negative interbuilding interactions.

The connected control method (CCM) is a SVC strategy for multibuilding systems that consists in linking adjacent buildings by coupling devices to provide appropriate reaction control forces. The application of the CCM using different types of passive [616], active [1719], and semiactive [2023] linking devices has been extensively investigated with positive results. Recently, more complex control configurations combining passive interbuilding dampers with local feedback control systems implemented in the buildings have been proposed [24, 25]. These active-passive SVC strategies combine the good properties of passive control systems and the high-performance characteristics of active control systems [2628]. It should be highlighted, however, that most of the research effort undertaken to date has been directed at the two-building case, while more complex multibuilding problems still remain virtually unexplored. Obtaining a suitable formulation for the dynamical response of certain classes of connected multistructure mechanical systems is one of the major obstacles that has to be overcome in order to design SVC strategies for multibuilding systems. A preliminary work in this line presenting an active-passive SVC strategy for seismic protection of a three-building system can be found in [29].

The main contribution of the present paper is twofold: (i) a mathematical model to compute the overall vibrational response of connected multistructure mechanical systems is provided. (ii) Active-passive SVC strategies for seismic protection of multibuilding systems are designed using the proposed model and the CCM approach.

The paper is organized as follows: in Section 2, a general second-order model for the unforced response of connected multistructure mechanical systems is provided. The forced response is also studied for some particular cases of special relevance in SVC. In Section 3, passive, active, and active-passive SVC strategies for seismic protection of multibuilding systems are discussed. The main ideas are presented by means of a three-building system. Finally, in Section 4, a set of numerical simulations is conducted to assess the effectiveness of the proposed control strategies.

2. Multistructure Connected System

In this section, we present a mathematical model to compute the dynamical response of the multistructure system schematically depicted in Figure 1. The overall system consists of parallel substructures . Each substructure is a mass-spring-damper system with degrees of freedom, and between adjacent substructures and , there is a linking system formed by a maximum number of spring-damper elements. The aim of this section is to obtain a proper formulation of the second-order equation that describes the overall motion of system in the form where is the global mass matrix; and are the total damping and stiffness matrices, respectively, including the internal stiffness and damping coefficients of the substructures as well as the stiffness and damping coefficients of the linking systems ; is the vector of external forces.

2.1. Unforced Response

Let us consider the th substructure displayed in Figure 2. The vector of relative displacements is where represents the relative displacement of the mass with respect to the fixed reference , which in this subsection is assumed to be an inertial frame.

A second-order model for the substructure can be written in the form where denotes the vector of interstructure forces resulting from the interaction between adjacent substructures through the linking elements. The mass matrix is a diagonal matrix and the damping matrix has the following tridiagonal structure: The stiffness matrix has an analogous structure and can be obtained by replacing entries by in (2.5). We also define the damping and stiffness matrices of the linking system as follows:

The main difficulty in obtaining a simple formulation for the overall second-order model (2.1) arises from the fact that adjacent substructures have, in general, different number of masses. This problem can be conveniently solved by extending the damping and stiffness matrices of the linking systems with a proper number of zero rows and columns. The benefits of this simple resource are twofold: (i) a plain and elegant matrix formulation of equation (2.1), and (ii) an extremely easy computational implementation. Next, we introduce the zero-extension of matrices and provide a simple Matlab function to compute it.

Definition 2.1. Given an matrix and two integers and , we define the zero-extension of as the matrix obtained from by adding final zero-rows and final zero-columns.
The following Matlab function computes the matrix zero-extension:
Function M=zex(A,m1,n1)
[m,n]=size(A);
M=[A zeros(m,n1n)
zeros(m1m,n1)].
For the matrix the zero-extension can be computed with the command zex(A,3,5), resulting

To obtain the expression for the vector of linking interstructure forces , we consider three different cases corresponding to the relative position of the substructure : (a) initial substructure , (b) interior substructure , , and (c) final substructure . For the initial substructure , from the force diagram in Figure 3, we have Equation (2.3) for takes now the form Note that, for simplicity, the explicit dependence on time has been omitted in (2.10), (2.11), and Figure 3, and notations like and have been used instead of and . The same will be done in the sequel when convenient.

Analogously, from the force diagram in Figure 4, it results and the second-order model for can be written as

Finally, from Figure 5, we get and the corresponding second-order model is

From (2.11), (2.13), and (2.15), we can now obtain an overall second-order model for the unforced response of the multibuilding coupled system in the form where is the overall vector of displacements. To this end, we express the global damping and stiffness matrices in the form where matrices and correspond to the internal damping and stiffness of the substructures, respectively, and have the following block diagonal form: and matrices , have the form given in (2.5). The damping matrix corresponds to the linking systems and has the tridiagonal block structure shown in Figure 6, the stiffness matrix has the same structure as and can be obtained by replacing the entries by . Finally, the global mass matrix is the block diagonal matrix where , are the substructure mass matrices given in (2.4).

2.2. Forced Response

Now, we assume that some external excitations are acting upon the substructures . Specifically, we will turn out our attention to the particular case schematically depicted in Figure 7, where represents the acceleration of the reference frame , and the element is a force actuation device implemented between the adjacent masses and that produces a pair of opposite forces of magnitude as indicated in the figure. This case is particularly relevant for structural vibration control of seismically excited buildings, where the external acceleration corresponds to the seismic ground acceleration, and the actuation devices are interstory force actuators that implement suitable control forces to mitigate the vibrational response of the building.

A second-order model for the vibrational response of the substructure can now be written in the form where the term is the vector of control forces acting on , and contains the inertial forces resulting from the fact that is now an accelerated reference frame. Denoting by the column vector with entries equal to 1, the vector of inertial forces can be written as For the vector of control actions, we consider the control location matrix of size and the vector of control actions to obtain Finally, considering (2.21), (2.22), (2.25), and the results presented in the previous subsection, we can derive a second-order model for the overall vibrational response of the multistructure system in the following form: where is the overall displacement vector defined in (2.17); matrices , , are given in (2.18), (2.19), (2.20), and Figure 6; is the external acceleration, and is the external disturbance matrix; represents the overall vector of actuation forces and is the overall location control matrix defined as is the total number of degrees of freedom, and is the number of substructures. If no active control system has been implemented in the subsystem , can be taken as a zero vector and as a zero matrix of appropriate dimensions. The proposed model includes the action of external acceleration disturbance and active control systems implemented in the substructures and, moreover, is formally analogous to the usual formulation used in single-structure SVC problems.

3. Structural Vibration Control Strategies for Multibuilding Systems

In this section, we are interested in designing SVC strategies for seismic protection of multibuilding systems. For clarity and simplicity, the main ideas are presented through the three-story building system schematically depicted in SubFigure 8(a), where the central five-story building is assumed to require a special level of seismic protection. For this particular multibuilding system, four control configurations are considered: (a) active-passive, (b) passive, (c) uncoupled-active, and (d) uncontrolled. In the active-passive control configuration (see SubFigure 9(a)), an active local state-feedback control system with the actuation scheme presented in SubFigure 8(b) has been implemented in the central building. Moreover, two passive dampers have been placed as interbuilding linking elements: one at the third-floor level between buildings 1 and 2 and the other at the second-floor level between building 2 and building 3. The passive control configuration (SubFigure 9(b)) only comprises the interbuilding passive dampers. In the uncoupled-active control configuration (SubFigure 9(c)), an active local feedback system has been implemented in the central building, but no passive interbuilding elements have been installed. Finally, no seismic protection is provided in the uncontrolled control configuration (SubFigure 9(d)), which will be used as a reference in the performance assessments.

The section has been structured in three parts. First, the results presented in Section 2 are applied to obtain a second-order model for the three-building system. Next, suitable state-space models are derived. Finally, a state-feedback LQR controller is designed to drive the active local feedback control system implemented in building 2.

To compute the LQR local controller, the following particular values of the building parameters have been used:  kg,  Ns/m,  N/m,  N/m,  N/m, for , , , , . The linking elements are considered as pure dampers with a damping constant = Ns/m and null stiffness; the value = indicates that no linking element exists at the th level between buildings and . The actuation elements , are assumed to be ideal force actuation devices, which are able to implement exactly the control actions producing the opposite pairs of control forces represented in Figure 8(b). These values will also be used in the numerical simulations conducted in Section 4.

3.1. Second-Order Model

Let us consider the three-story building system displayed in Figure 8(a) as a lumped-mass planar system with displacements in the direction of the ground motion. In this case, the multibuilding system can be represented by the connected multistructure system shown in Figure 10. Using the results presented in the previous section, a second-order model in the form to describe the buildings motion can be easily obtained. The overall vector of story displacements with respect to the ground is where represents the displacement of the th story in the th building. The mass matrix is with The total damping matrix can be written in the form where and the matrix corresponding to the linking elements has the following block tridiagonal structure: where denotes the zero-extension of , for example To obtain the total stiffness matrix matrices , can be computed replacing the damping coefficients , by the corresponding stiffness coefficients , in (3.7), (3.8), (3.10), and matrices , by , in (3.6), (3.9). For the active-passive control configuration depicted in Figure 9(a), the vector of control actions is and the control location matrix to produce the corresponding control forces can be written as follows: Finally, the disturbance input matrix is

3.2. First-Order State-Space Model

Now, we take the state vector and derive the first-order state-space model where the state, control, and disturbance input matrices are, respectively, Regarding the output, we consider two different cases: interstory drifts and interbuilding approaches. The interstory drifts represent the relative displacements between consecutive stories in the th building and are defined by where is the number of stories in building . The vector of interstory drifts can be obtained with the output matrix where The interbuilding approaches describe the approaching between the stories placed at the th level in the adjacent buildings , and are defined by where . The vector of interbuilding approaches can be computed with the output matrix Finally, let us suppose that the state-feedback controller has been computed to drive a local active control system in . We write the local vector of control actions as where matrices , are obtained by splitting the control matrix after the -th column. The seismic response of the overall three-building system for different active-passive control configurations can be computed using the closed-loop state-space model as follows: where the state matrix can be obtained using the matrices , , given in (3.18), and the overall control matrix with In particular, for the active-passive control configuration depicted in Figure 9(a), the overall control matrix has the form

3.3. Local State-Feedback Controller Design

To compute a local state-feedback LQR controller [30] for the actuation system in building , we consider the local second-order model where is the vector of story displacements relative to the ground, is the vector of control actions, and matrices , , , have been given in the previous subsection. From (3.32), we obtain the first-order state-space model with local state vector state matrix and control input matrix To obtain the local vector of interstory drifts we take the matrix given in (3.22) and define the local output matrix Next, we consider the weighting matrices and define the quadratic cost function to compute a local state-feedback LQR controller with the following control gain matrix:

4. Numerical Simulations

In this section, the vibrational response of the three-building system presented in Section 3 is computed for several control configurations. Specifically, the maximum absolute interstory drifts and maximum interbuilding approaches are computed for three control configurations: (a) active-passive, (b) passive, and (c) uncoupled-active, which are schematically depicted in Figures 9(a), 9(b), and 9(c). The vibrational response of the uncontrolled system (SubFigure 9(d)) is also computed, and it is used as a natural reference in the performance assessment. In all the cases, the full-scale North-South El Centro 1940 seismic record obtained at the Imperial Valley Irrigation District substation in El Centro, CA, during the Imperial Valley earthquake of May 18, 1940, has been used as a ground acceleration input (see Figure 11).

The maximum absolute interstory drifts are displayed in Figure 12. Looking at the central graphic, the excellent behavior of the active-passive (black asterisks) and the uncoupled-active (blue circles) control configurations can be clearly appreciated. In fact, the data in Table 1 indicate that these active control configurations attain reductions of about 70% in the peak interstory drift values with respect to the uncontrolled response. For the lateral buildings, however, the situation is totally different. In this case, the active-passive control configuration produces a lower but still significant reduction of the interstory drifts, while no seismic protection is provided by the uncoupled-active configuration.

Regarding the interbuilding approaches, we can see in Figure 13 that interbuilding separations of about 7.5 cm would have resulted in interbuilding collisions for the uncontrolled configuration. In contrast, interbuilding separations of about 2.5 cm can be considered safe for the active-passive control configuration. An important reduction in the interbuilding approaches is also achieved by the uncoupled-active configuration, but the data in Table 2 indicate that the percentages of reduction obtained by this configuration are about 25 points inferior to those obtained by the active-passive control configuration.

To complete the comparison between the active-passive and the uncoupled-active configurations, the corresponding maximum absolute control efforts are presented in Table 3. The values in the table indicate that the active-passive configuration requires a slightly higher level of control effort. However, considering the superior performance exhibited by the active-passive configuration, the extra cost is certainly small.

The behavior of the passive control configuration is also remarkable. Despite its simplicity and null power consumption, percentages of reduction in the interstory drifts peak values of about 45% are achieved in buildings 2 and 3 and around 20% in building 1. Reductions of about 60% are also produced for the interbuilding approaches.

Finally, it should be highlighted the robustness of the active-passive control configuration against failures in the local active control system. Actually, in case of a full failure of the active control system, the passive level of seismic protection can still be guaranteed by the passive-active control configuration. In contrast, the same kind of failure in the uncoupled-active configuration would produce a total loss of seismic protection.

5. Final Remarks and Conclusions

In this work, a mathematical model to compute the overall vibrational response of connected multistructure mechanical systems has been presented. Using the proposed model and following the connected control method approach, structural vibration control strategies for seismic protection of multibuilding systems can be efficiently designed. As a practical application of the new ideas, different control configurations for seismic protection of a particular three-building system have been designed. For these control configurations, numerical simulations of the three-building system vibrational response have been conducted using the full-scale North-South 1940 seismic record as a seismic excitation. The simulation results come to confirm the excellent properties of control configurations that combine passive interbuilding dampers with local feedback control systems implemented in the buildings. These hybrid active-passive control strategies possess the good properties of passive control systems and also have the high-performance characteristics of active control systems. Moreover, active-passive control configurations can be properly designed for multibuilding systems that require different levels of seismic protection and are also remarkably robust against failures in the local feedback control systems. Finally, it is worth highlighting that the proposed active-passive control strategy is compatible with practically any control design methodology of the local feedback control systems and also with semiactive implementations of the actuation systems. Consequently, further research effort needs to be aimed at exploring more complex scenarios involving issues of practical interest such as wireless implementation of the communications systems [31], actuator saturation [32], actuation and sensor failures [33], structural information constraints [34, 35], uncertain stochastic networked systems [3638], or limited frequency domain [39].