Decay Heat Removal in GEN IV Gas-Cooled Fast Reactors
Table 5
Timing of significant events for case 32.
0s
10 sq. in break initiated.
169.3s
Reactor tripped on low-pressure. Generator tripped off line and turbine bypass is opened.
234.92s
Turbine bypass reclosed when PCU flow dropped below 20% of rated value.
382.92s
Compressors replaced by dummy volumes when PCU flow again dropped below 20% of rated value.
420s
Blower turned on with a flow velocity of 3.5 m/s.
1250s
Helium accumulator connected to guard containment to maintain pressure at 800 kPa. Accumulator is modeled by a time-dependent volume of constant pressure (800 kPa) and constant temperature (303.15 K)
9000s
Case restarted by defining reactor power as a function of time in the form of a table. Reactor power decayed linearly from 26.2589 MW at seconds to 13.9748 MW at seconds. The later power level is equivalent to the decay power 24-hours after a shutdown.
9050s
Trip valve located at the junction between the PCU outlet and the reactor downcomer was closed. This was used to simulate the action of a check valve that would have prevented flow from entering the PCU via the reactor downcomer.
15000s
Blower speed reduced to zero in 5 seconds. Reactor power was maintained constant at the 24-hour decay heat level.