Pressure Losses across Multiple Fittings in Ventilation Ducts
Table 4
Effect of upstream fitting(s) on pressure loss (Pa) across a downstream fitting.
(a) Base case: Case 1 |
| Re = | Case 1 | Case 7 | | | |
| Pressure loss | 72 | 66 | 66 | Percentage decrease | | | 8.3% |
|
|
(b) Base case: Case 2 |
| Re = | Case 2 | Case 8 | Case 10 | Case 15 | | | | | | | | |
| Pressure loss | 204 | 64 | 185 | 190 | 172 | 208 | 198 | 180 | Percentage decrease | | | 9.3% | | 15.7% | | 2.9% | 11.8% |
|
|
(c) Base case: Case 3 |
| Re = | Case 3 | Case 9 | Case 11 | Case 12 | | | | | | | |
| Pressure loss | 944 | 54 | 588 | 184 | 774 | 1030 | 750 | Percentage decrease | | | 37.7% | | 18.0% | | 20.6% |
|
|
(d) Base case: Case 5 |
| Re = | Case 5 | Case 13 | Case 14 | | | | | | |
| Pressure loss | 150 | 144 | 150 | 142 | 154 | 118 | Percentage decrease | | | 0.0% | | −2.7% | 21.3% |
|
|