Research Article

Synthesis of Trigeneration Systems: Sensitivity Analyses and Resilience

Table 6

Sensitivity analysis for fam considering the base case configuration.

fam (yr−1)0.100.150.200.250.30

System composition
 Gas engines 33333
 Hot water boilers 33333
 Heat exchangers 44444
 Absorption chillers 11111
 Mechanical chillers 33333
 Cooling towers 33333

Natural gas (total) MWh/yr37,32437,32437,32437,32437,324
Purchased electricity MWh/yr2929292929
Sold electricity MWh/yr11,38911,38911,38911,38911,389
Natural gas (cogeneration) MWh/yr36,63836,63836,63836,63836,638
Cogenerated electricity MWh/yr14,95414,95414,95414,95414,954
Cogenerated useful heat MWh/yr86028602860286028602

Primary energy savings %10.0110.0110.0110.0110.01
Equivalent electrical efficiency %55.2255.2255.2255.2255.22

Annual fixed cost €/yr255,415383,122510,830638,538766,245
Cost of natural gas €/yr933,092933,092933,092933,092933,092
Cost of electricity €/yr32073207320732073207
Profit with the sale of electricity €/yr−876,960−876,960−876,960−876,960−876,960

Annual total cost €/yr314,754442,462570,169697,877825,584