Development and Application of a ZigBee-Based Building Energy Monitoring and Control System
Table 3
Power consumption data for two electric heaters (kWh).
| Time (h) | 1.00 | 8.17 | 9.35 | | |
| C: ZBEMCS | Branch 1 | 0.609 | 8.838 | 15.779 | | | Branch 2 | 1.508 | 18.633 | 7.278 | | | Trunk | 2.117 | 27.471 | 23.057 | | |
| D: standard wattmeter | Branch 1 | 0.7 | 8.9 | 15.8 | | | Branch 2 | 1.6 | 18.7 | 7.3 | | | Trunk | 2.3 | 27.6 | 23.1 | | |
| Power on nameplate (kW) | Branch 1 | 0.6 | 1.0 | 1.6 | | | Branch 2 | 1.5 | 2.2 | 0.7 | | | Trunk | 2.1 | 3.2 | 2.3 | | |
| E: nominal power | Branch 1 | 0.6 | 8.170 | 14.960 | | | Branch 2 | 1.5 | 17.974 | 6.545 | | | Trunk | 2.1 | 26.144 | 21.505 | Average deviation | Standard deviation |
| C−D | Branch 1 | −0.091 | −0.062 | −0.021 | −0.058 | 0.035 | Branch 2 | −0.092 | −0.067 | −0.022 | −0.060 | 0.035 | Trunk | −0.183 | −0.129 | −0.043 | −0.118 | 0.071 |
| C−E | Branch 1 | 0.009 | 0.668 | 0.819 | 0.499 | 0.431 | Branch 2 | 0.008 | 0.659 | 0.733 | 0.467 | 0.399 | Trunk | 0.017 | 1.327 | 1.552 | 0.965 | 0.829 |
| D−E | Branch 1 | 0.100 | 0.730 | 0.840 | 0.557 | 0.399 | Branch 2 | 0.100 | 0.726 | 0.755 | 0.527 | 0.370 | Trunk | 0.200 | 1.456 | 1.595 | 1.084 | 0.768 |
|
|