Research Article

Case Study of Remaining Service Life Assessment of a Cooling Water Intake Concrete Structure in Indonesia

Table 5

Corrosion thickness of rebar.

NumberCodeRebar diameterTrainCorrosion thicknessCorrosion rate (mm/year)Microstructure

1Core 3 19A/B10~20 µm0.0003–0.0006Pearlite and Ferrite
2Core 8 19C/D20~50 µm0.0007–0.0017Pearlite and Ferrite
3Core 15 19G/H3~8 mm0.1875–0.5Pearlite and Ferrite