Fire scenario design for this study.
| Fire location | Fire scenario | Fire growth factor (kW/s2) | Sprinkler system | Smoke extraction system | Maximum heat release rate of fire (MW) |
| F1 shop A | A00 | 0.04689 | Invalid | Invalid | 8.0 | A01 | 0.04689 | Invalid | Valid | 8.0 | A10 | 0.04689 | Valid | Invalid | 5.0 | A11 | 0.04689 | Valid | Valid | 5.0 |
| F4 restaurant B | B00 | 0.04689 | Invalid | Invalid | 8.0 | B01 | 0.04689 | Invalid | Valid | 8.0 | B10 | 0.04689 | Valid | Invalid | 2.5 | B11 | 0.04689 | Valid | Valid | 2.5 |
| F15 an office area C | C00 | 0.04689 | Invalid | Invalid | 6.0 | C01 | 0.04689 | Invalid | Valid | 6.0 | C10 | 0.04689 | Valid | Invalid | 1.5 | C11 | 0.04689 | Valid | Valid | 1.5 |
| F14 an office area and staircase D | D00 | 0.04689 | Invalid | Invalid | 6.0 | D01 | 0.04689 | Invalid | Valid | 6.0 | D10 | 0.04689 | Valid | Invalid | 1.5 | D11 | 0.04689 | Valid | Valid | 1.5 |
| F14-15 an office area and staircase E | E00 | 0.04689 | Invalid | Invalid | 6.0 | E01 | 0.04689 | Invalid | Valid | 6.0 | E10 | 0.04689 | Valid | Invalid | 1.5 | E11 | 0.04689 | Valid | Valid | 1.5 |
| F14-15-16 an office area and staircase F | F00 | 0.04689 | Invalid | Invalid | 6.0 | F01 | 0.04689 | Invalid | Valid | 6.0 | F10 | 0.04689 | Valid | Invalid | 1.5 | F11 | 0.04689 | Valid | Valid | 1.5 |
|
|