Numerical Simulation of Fire Smoke Spread in a Super High-Rise Building for Different Fire Scenarios
Table 6
Critical time required for fire to become a hazard for the three functional rooms.
| Fire location | Fire scenario | Critical time required for fire to become a hazard (s) |
| F1 shop area A | A00 | 184 | A01 | 196 | A10 | 191 | A11 | 212 |
| F4 catering area B | B00 | 190 | B01 | 196 | B10 | 194 | B11 | 214 |
| F15 an office area C | C00 | 119 | C01 | 121 | C10 | 124 | C11 | 133 |
|
|