Simulation Analysis and Scheme Optimization of Energy Consumption in Public Buildings

Table 6

Design parameters of the building envelope energy-saving potential sequencing and recommended values.

Design parameters of building envelopeSensitivity coefficientSortingRecommended values
MaximumMinimumAverage

The comprehensive heat transfer coefficient of the exterior wall0.01200.00990.01115≤0.5 W/(m2·K)
The comprehensive heat transfer coefficient of the roof0.00130.00090.00116As small as possible, if the criterion is met
The comprehensive heat transfer coefficient of the external windows0.03850.03180.03523As small as possible, if the criterion is met
The solar heat coefficient of the outer window0.02070.01180.016640.3795 W/(m2·K)∼0.44 W/(m2·K)
The ratio of the window to the wall0.04810.03540.04162As small as possible, if the functionality is met
The airtightness of the outer window0.04960.04570.04741The higher the level is, the more feasible the technology and economy are. The recommendation is above level 4