Research Article
A Fuzzy Logic Controller to Increase Fault Ride-Through Capability of Variable Speed Wind Turbines
Table 2
Results obtained with PI controller and without controller for all WFs.
| WF no. | Proposed controller | PI controller | Without controller | Voltage (p.u.) | WF’s situation | Voltage (p.u.) | WF’s situation | Voltage (p.u.) | WT’s situation |
| 1 | 0.745 | Connected | 0.698 | Disconnected | 0.688 | Disconnected | 2 | 0.740 | Connected | 0.695 | Disconnected | 0.685 | Disconnected | 3 | 0.715 | Connected | 0.715 | Connected | 0.691 | Disconnected |
|
|