Abstract

The paper presents a measurement system of peak value of high voltage (H.V.) using 150 mm diameter sphere gap, disposed in vertical position. Experimental breakdown results have been compared with standard values at atmospheric reference conditions STC (20°C, 101.3 kPa, or 760 mmHg). The main experimental and theoretical characteristics are presented.

1. Introduction

Choosing the most suitable method for measuring high voltage depends on the measured voltage value, on the available measuring devices, and on whether the need is to measure the peak or the effective value. It is known that spark gap spheres measure the peak AC voltage with a precision of ±3%. The breakdown voltage depends on the distance between the spheres, on the spheres diameter, and on the type of voltage: direct, alternating, or impulse. The breakdown voltage is a nonlinear function of the gap distance which is due to the increasing field inhomogeneity [1]. Sphere gaps can be arranged vertically, with the lower sphere grounded, or horizontally. In both cases, one must take into account the parameters and which define the field distribution between the two spheres that are closest to each other. For 150 mm sphere diameter, the minimum value of is and the maximum value is (where is the sphere diameter) while the minimum value for parameter minimum is (where is the spacing) [2, 3].

Sphere gap can be considered as an approved calibration device, with a limited accuracy, but with high reliability and simplicity [4]. The breakdown field distribution can be controlled by the geometry of the electrode and by the air density. In some cases, the spark gap needs to be irradiated with ultraviolet light or X-rays sources in order to obtain consistent values for smaller sphere gaps, with the gap spacing less than 1 cm [3, 4].

The breakdown voltage of a sphere gap is affected by some factors: atmospheric conditions, nearby earthed objects, voltage ramp-up time, and irradiation which is necessary when the diameter of the sphere gap is less than 10 cm and measured voltage below 50 kV [36]. The breakdown probability depends on the air density and on ion density in the air. Therefore, in the successive breakdown experiments it is necessary to have identical ion densities in the gas gap, before every new voltage application [7, 8]. The factors that can modify the breakdown voltage have been analyzed in the scientific literature [4, 9, 10]. The breakdown voltage increases with humidity. The increase is about 2-3 percent for normal humidity values between 8 and 15 g/m3 [4]. For sphere gaps spacing less than one meter the effect of humidity can be ignored [8].

The breakdown voltage depends on the temperature and pressure. Experimental values related to standard conditions (STC) (20°C, 101.3 kPa, or 760 mmHg) must be multiplied with air the density factor () [8, 11]: where is the breakdown voltage under test conditions, is the breakdown voltage at STC, and is a function of air density factor.

The air density factor is given by the following equation [11]: where is the air pressure at standard conditions (760 mmHg), is the air pressure at test conditions, is the temperature at standard condition (20°C), and is the temperature at test conditions. The relation between the correction factor and the air density factor is known in scientific literature [3, 4, 9, 11, 12].

In a nonuniform field the autonomy condition of breakdown may be used. Considering this condition the similarity law of breakdowns can be established: “in a nonuniform field, at constant temperature, the breakdown voltage depends on the and on the reports of all other geometric dimensions of the gap and the distance ” [8, 13]:

The scientific literature gives an empirical relationship for the calculation of the breakdown voltage between two identical spheres [8]: where is the gap spacing in cm, is the radius of the sphere, and is the air density factor.

To measure high voltage with spark gap spheres it is necessary to use a noninductive protection resistance between the source and the sphere gap, in order to limit the breakdown current. The value of the series resistance can vary from 100 kΩ to 1000 kΩ for alternating voltages and less than 500 Ω for impulse voltages [3]. The applied voltage is uniformly increased until breakdown occurs in the sphere gap. Usually, a mean of about three breakdown values is taken into account, with an accuracy of ±3%.

2. Experimental Setup

For measuring the peak values we used experimental spark gap spheres, in vertical arrangement. Two metal spheres of equal diameters, with smooth surfaces and uniform curvature, were used in the experiment. The upper sphere is connected to a 0–180 kV high voltage AC power source through a noninductive resistor of 100 kΩ. The bottom sphere is connected to the ground with the possibility of vertical position changing towards the upper sphere by a DC electrical engine.

The distance between the spheres with 150 mm in diameter was modified in steps of 0.5 cm from 1 cm to 6 cm. The block diagram of the experimental test bench is presented in Figure 1. To measure the breakdown voltage, a high voltage probe (Hameg probe) with 1000 : 1 voltage division ratio and a multimeter (Meterman 38XR) was used. The high voltage probe was connected to a Tektronix TDS 2024C (200 MHz, 2 GS/s) oscilloscope, to view the shape of the breakdown voltage waveform. The temperature and relative humidity have been measured with a Lutron LM-8000 meter with the following specifications: relative humidity between 10 and 95%RH (0, 1%RH accuracy) and temperature between 0 and 50°C (0, 1°C accuracy). The block diagram of the test bench is presented in Figure 1.

The arrangement for the construction of the sphere gap is shown in Figure 2, where parameters and are defined. The sparking point which is established by parameter must be within given limits related to the sphere diameter , [11]. In order to be considered as a standard measuring device, a minimum value for around the sphere must be available. Also, the surfaces of the sphere near the sparking point should be free of irregularities or grease.

2.1. Test Conditions

All the experiments were carried out at room temperature 19°C, air pressure 760.56 mmHg, absolute humidity 8.13 g/m3, and 50% relative humidity. For a given distance between the spheres, three successive measurements were made. The final value of the breakdown voltage was determined as the average of five successive measurements, with an error of less than 3%.

Various studies have been made over the time concerning the time gap between two consecutive breakdowns [14, 15]. For the scope of the present work this time gap has been set to at least one minute.

The experimental test setup presented below (Figure 3) is used to measure the AC high voltage, 50 Hz, applied to the sphere gap. The breakdown voltage is measured by modifying the gap spacing from 1 cm up to 6 cm, according to the available standards [11]. All the components of the spark gap spheres were made of insulating materials.

3. Results

The standard peak values of breakdown voltage (), in air, for symmetrical spheres of 150 mm in diameter, have been corrected to the standard temperature and pressure according to relations (1) and (2). The experimental data are listed in Table 1. Corrections were made for standard peak values at STC, according to recommended standards. The relative humidity has not been considered. The breakdown voltages measured at test conditions are close to the standard peak values. The errors between the measured breakdown voltages and the standard ones are less than 3%, except for those measured at 4 and 6 cm.

Figure 4 shows the variation of measured breakdown voltages and standard peak voltages at STC, as a function of gap spacing. For comparison, Figure 4 represents also the theoretical breakdown voltages obtained through (4), as a function of gap spacing. The maximum difference between and is less than 1%. The variation of breakdown strength, in /cm, for different gap spacing in atmospheric air at constant pressure, is presented in Figure 5.

Sphere gaps are used for voltage measurements and have only limited range with uniform electric field. In this respect, Rogowski proposed a design for uniform field electrodes for breakdown voltages up to 600 kV. It is known that it is not possible to ensure that the sparking always takes place along the uniform field region [3]. In scientific literature are presented breakdown voltage data for uniform fields. Table 2 gives a comparison between the breakdown voltages at STC of a uniform field electrode gap (measured by Ritz and Schumann) a sphere gap [3], and the values obtained in this work.

From the data in Table 2 we can observe that there is no major difference between the breakdown voltages of sphere gaps and the uniform field gaps, at least at small distances between spheres.

The values obtained for the proposed sphere gap (Figure 2) are approaching the ones measured by Ritz and Schumann with specific errors, possibly related to rise time of voltage waveforms, electrodes shape and material, and so forth.

4. Conclusions

The breakdown voltages in air, at constant pressure, in nonuniform field, have been measured for AC high voltage, for different gap values between the spheres. It has been shown that the breakdown voltage increases with the gap spacing almost linearly. The accuracy of experimentally determined breakdown voltages has been verified and compared with theoretical values listed in the standards.

The numerical values of experimental breakdown voltages for the 4 cm and 6 cm gap spacing show an error above 3%, compared to the values specified in standards. These errors can be attributed to the nonuniform field, which increases as the distance between the spheres is increased.

Conflict of Interests

The authors declare that there is no conflict of interests regarding the publication of this paper.