| Operating problem | Corrective action | FACTS devices |
| (i) Voltage limit: | (a) Low voltage at heavy load | Supply reactive power | STATCOM, SVC | (b) High voltage at low load | Absorb reactive power | STATCOM, SVC, TCR | (c) High voltage following an outage | Absorb reactive power; prevent overload | STATCOM, SVC, TCR | (d) Low voltage following an outage | Supply reactive power; prevent overload | STATCOM, SVC | (ii) Thermal limits: | (a) Transmission circuit overload | Reduce overload | TCSC, SSSC, UPFC, IPC, PS | (b) Tripping of parallel circuits | Limit circuit loading | TCSC, SSSC, UPFC, IPC, PS | (iii) Loop flows: | (a) Parallel line load sharing | Adjust series reactance | IPC, SSSC, UPFC, TCSC, PS | (b) Post-fault power flow sharing | Rearrange network or use thermal limit actions | IPC, TCSC, SSSC, UPFC, PS | (c) Power flow direction reversal | Adjust phase angle | IPC, SSSC, UPFC, PS |
|
|