Exposed surface: water film on the exposed surface |
|
Date of test: May 22, 2014 | Indoor temperature: 32.4°C Indoor humidity: 63% |
|
Heating test duration (h:m:s) | Test observations |
|
0:00:−30 | Switch on water circulation system 30 seconds before heating |
|
0:00:00 | Heating begins (roller door upwarp of roller door bottom bed plate is 0 cm) |
|
0:20:00 | Fill 200 L water in water tank |
|
0:27:40 | Temperature measured by handheld thermocouple at unexposed surface measuring point TC#_9 is 51°C |
|
0:29:53 | Temperature measured by handheld thermocouple at unexposed surface measuring point TC#_7 is 50°C |
|
0:30:00 | Fill 240 L water in water tank |
|
0:43:00 | Fill 260 L water in water tank |
|
0:50:00 | Fill 280 L water in water tank |
|
0:55:00 | Roller door upwarp is 0 cm |
|
0:59:00 | Temperature measured by handheld thermocouple at unexposed surface measuring point TC#_7 is 55.9°C |
|
0:59:50 | Temperature measured by handheld thermocouple at unexposed surface measuring point TC#_9 is 60.6°C |
|
1:00:00 | Fill 320 L water in water tank |
|
1:10:00 | Fill 340 L water in water tank |
|
1:20:00 | Fill 280 L water in water tank |
|
1:25:50 | Temperature measured by handheld thermocouple at unexposed surface measuring point TC#_7 is 68.4°C |
|
1:26:30 | Temperature measured by handheld thermocouple at unexposed surface measuring point TC#_9 is 61.3°C |
|
1:30:00 | Fill 260 L water in water tank |
|
1:40:00 | Fill 260 L water in water tank |
|
1:50:00 | Fill 220 L water in water tank |
|
1:52:00 | Temperature measured by handheld thermocouple at unexposed surface measuring point TC#_8 is 79.5°C |
|
1:53:00 | Temperature measured by handheld thermocouple at unexposed surface measuring point TC#_7 is 70.2°C |
|
1:54:00 | Temperature measured by handheld thermocouple at unexposed surface measuring point TC#_9 is 59.6°C |
|
2:00:00 | Stop heating; roller door upwarp is 0 cm, not exceeding 1.91 cm |
|