Table 5

Diagnosis efficiency of the preliminary FDD and the FDD with Tc acquittal.

TypeBiasThe preliminary FDDThe FDD with Tc acquittal
FDR (%)MDR (%)Time (s)FDR (%)MDR (%)Time (s)

Fixed bias of Tsup sensor0.525.280.120.01541.801.670.0156
1.02.770.000.01530.000.000.0155
1.51.300.000.01520.000.000.0154

Fixed bias of Twr sensor0.525.392.590.01420.172.980.0144
1.025.262.470.01460.222.470.0149
1.525.262.510.01500.302.510.0153

Fixed bias of Tws sensor0.531.834.710.01337.964.800.0136
1.031.275.360.01338.745.360.0136
1.530.454.410.01457.354.410.0147

Fixed bias of Mw sensor5%22.196.960.014312.246.960.0146

Note: cases that MDR increased are marked in bold.