Studying the Effect of Stray Capacitance on the Measurement Accuracy of the CVT Based on the Boundary Element Method

Table 1

Comparison of calculated and measured voltages at four different medium-voltage tap positions.

Position (m)Measured voltage (kV)Calculated voltage (kV)Maximum deviation rate of voltage (%)

0.1816.840 ± 1.5 × 10−316.8420.021
0.2018.706 ± 1.5 × 10−318.7070.013
0.2220.582 ± 1.5 × 10−320.5810.012
0.2422.461 ± 1.5 × 10−322.4590.015