Studying the Effect of Stray Capacitance on the Measurement Accuracy of the CVT Based on the Boundary Element Method
Table 1
Comparison of calculated and measured voltages at four different medium-voltage tap positions.
| Position (m) | Measured voltage (kV) | Calculated voltage (kV) | Maximum deviation rate of voltage (%) |
| 0.18 | 16.840 ± 1.5 × 10−3 | 16.842 | 0.021 | 0.20 | 18.706 ± 1.5 × 10−3 | 18.707 | 0.013 | 0.22 | 20.582 ± 1.5 × 10−3 | 20.581 | 0.012 | 0.24 | 22.461 ± 1.5 × 10−3 | 22.459 | 0.015 |
|
|