Design and Simulation of a Solar Chimney PV/T Power Plant in Northwest China

Table 4

Comparison of PV model power, PVT power contribution, and total PV-related power contribution (PV + PVT) in the present study and the PV power generation without airflow cooling by taking PV power generation under ambient temperature as a reference.

Month123456789101112Average

PV power generation under ambient temperature, PPV_TaValue/MW17.1517.5123.1324.3625.9126.6425.4624.2523.1419.4815.4615.1721.47
Percentage to PPV_Ta/%100.00100.00100.00100.00100.00100.00100.00100.00100.00100.00100.00100.00100.00

PV model power in the present studyValue/MW17.1517.0921.0021.0721.5021.5020.4819.8519.7017.7015.0315.1718.94
Percentage to PPV_Ta/%100.0097.6090.7986.4982.9880.7180.4481.8685.1390.8697.22100.0088.19

PVT power contribution in the present studyValue/MW0.850.851.131.161.221.231.161.101.080.910.720.731.01
Percentage to PPV_Ta/%4.964.854.894.764.714.624.564.544.674.674.664.814.72

Total PV-related power contribution (PV + PVT)Value/MW18.0017.9422.1322.2322.7222.7321.6420.9520.7818.6115.7515.9019.95
Percentage to PPV_Ta/%104.96102.4695.6891.2687.6985.3285.0086.3989.8095.53101.88104.8192.91

PV power generation without airflow coolingValue/MW12.2712.7715.5616.6717.6818.2918.1717.6216.6914.5712.0011.3915.31
Percentage to PPV_Ta/%71.5572.9367.2768.4368.2468.6671.3772.6672.1374.7977.6275.0871.29