Abstract

This paper proposes a coordinated optimal control strategy of PV generators and air-conditioning loads, in order to handle the possible voltage beyond limit issues resulting from high penetration of PV generators in the distribution networks. This strategy is achieved via coordinately considering the node voltage sensitivity and the adjustment-compensation bid model, to improve the economy of the whole system. As a result, the shortage of the PVs’ reactive power control capability is compensated by the adjustable air-conditioning loads, so that the waste of the photovoltaic power can be reduced or even avoided. The case study using an IEEE standard 33-node system, which is further updated with the installation of 5 PV generators and 5 air-conditioning loads, validates the correctness and effectiveness of the proposed control strategy.

1. Introduction

As the problem of energy shortage and environmental pollution is more critical, access of a distributed generator (DG) such as PV and wind power to the distribution network has become an important trend of distribution network development. Distributed PV access to the distribution network can realize the local balance of energy, cut the investment, and reduce the loss of long-distance power transmission. At the same time, making use of clean and renewable PV power can replace traditional fossil energy and improve energy structure. Due to the randomness and volatility of the PV power, a large number of distributed PV access also bring power quality problems, such as voltage fluctuation and flicker and voltage off-limit to the power grid [1], which endanger the safe and stable operation of the power grid.

The problem of voltage off-limit has become one of the main factors restricting the scale and permeability of distributed PV power in the distributed network [2]. When the PV output is high and the load is light, it may easily cause the problem of voltage off-limit [3]. Traditional solutions are generally focused on the supply side, and the main solutions are adjusting the reactive power of the PV inverter [4], installing reactive-load compensation equipment such as a reactor [5], and calling energy storage equipment to absorb the extra PV power [6, 7]. If necessary, the measure of removing part of active power, namely, “waste of PV power,” must be taken [8].

During the scheme above, due to the limit of the power factor, adjusting the reactive power of the inverter has limited effect on voltage adjustment, and the installing of reactive compensation equipment and energy storage equipment brings additional investment. The “waste of PV power” reduces the utilization of renewable energy. If the voltage can be ensured under the limit and the economy can be improved at the same time, it will promote the scale and permeability of distributed PV in the distribution network.

With the deeper research of smart grid and demand-side response, more and more researchers begin to pay attention to the great potential of flexible loads such as air-conditioning in power system regulation [9]. At present, relevant researches mainly focus on the establishment of an air-conditioning load model [10], the prediction of air-conditioning load [11], and air-conditioning load participating in peak load regulation and frequency modulation [10, 12]. If the regulation ability of an air-conditioning load can be used, though increasing air-conditioning power to consume the excessive PV power, it will be able to make up for the inadequacy of photovoltaic reactive power regulation ability and at the same time reduce the waste of PV power and the investment of energy storage and reactive compensation equipment, which provides a new method to solve the problem of voltage off-limit.

This paper considers the regulation potential of the air-conditioning load which coordinates with the voltage adjustment ability of PV itself and puts forward a voltage control strategy for the distribution network of coordinated optimization of photovoltaic and air-conditioning loads. In the distribution network, when voltage exceeds the limit due to the excess photovoltaic output, based on the voltage sensitivity and the pricing model of photovoltaic and air conditioner, the PV reactive power, air-conditioning load and PV active power regulation is allocated, so that the voltage limit control can be realized at the lowest amount of compensation. At the same time, this strategy maximizes the amount of photovoltaic power generation. On the other hand, the air conditioner user gets the compensation during the regulation, and after the adjustment, it can also maintain indoor temperature at a relatively low power. This strategy takes into account the benefits of the photovoltaic, air conditioner, and power grid side, which has high economic efficiency.

2. The Pricing Model of PV and Air-Conditioning

2.1. Adjustment-Compensation Bid Model of PVs

When using the reactive voltage regulation capability of PV, the maintenance cost should be taken into consideration: where is the compensation price for the reactive power adjustment of PV and is the maintenance cost of PV adjusting reactive power.

When using the active voltage regulation capability of PV, the maintenance cost and the loss of power should be taken into consideration: where is the compensation price for the active power adjustment of PV; is the selling price of electricity, is the maintenance cost of PV adjusting active power; is the user preference coefficient, which is determined by each user; and is the amount of active power adjustment.

2.2. Adjustment-Compensation Bid Model of Air-Conditioning Loads

In this paper, the adjustment-compensation bid model of air-conditioning loads is formulated by the following steps: first, users define their temperature-compensation model based on their choices between comfort and earning. Then the adjustment-compensation model is formulated by combining the temperature-compensation model and the thermodynamic model of the building where the air-conditioning is located.

2.2.1. Temperature-Compensation Model

The temperature-compensation model is shown in Figure 1, where , , and are user-specified maximum, minimum, and desired indoor temperatures, respectively; is the average compensation price of a certain price history; is the standard variation of the compensation prices during the given history; is the user preference coefficient, which is determined by each user; and the ΔT part in Figure 1 shows the adjustable range [13].

The curve in Figure 1 can be expressed as the following piecewise function: where is the compensation price for air-conditioning and , , , and are coefficients.

2.2.2. Thermodynamic Model of the Building Where the Air-Conditioning Is Located

In this paper, the equivalent thermal parameter (ETP) model is used in the thermodynamic model of the building where the air-conditioning is located, which is shown in Figure 2 [14].

The ETP model has the following expression: where is the equivalent heat capacity, is the equivalent heat resistance, is the outside temperature at time, is the indoor temperature at time, is the average power from time to time, COP is the energy efficiency, and is the time interval.

By combining (3) with (4) and (5), the adjustment-compensation model is finally formulated with the following expression: where is the minimum air-conditioning power, which is equal to the larger value between 0 and air-conditioning power when , and is the maximum air-conditioning power, which is equal to the smaller value between the rated power and the power when .

3. Coordinate Optimization Control Strategy of PV and Air-Conditioning Load

3.1. Overall Framework

Figure 3 shows the coordinative optimization control strategy of photovoltaic and air-conditioning load. When the distribution network exists at the voltage limit, voltage-centralized controllers make a power flow calculation online in the distribution network. Based on the Jacobi matrix, this paper deduces the active and reactive power sensitivities of all nodes related to PV or air-conditioning. Meanwhile, each PV and air-conditioning submits its own adjustment quantity-compensation price model. After sensitivities and adjustment, a quantity-compensation price model is built; the target is to minimize the total compensation. The objective function is established by considering constraints which relate to voltage overlimit elimination, power limit at each node, and users’ comfort index. The objective function is resolved to optimize the adjustment of each PV and air-conditioning. Each PV and air-conditioning gains access to the regulation information. According to the adjustment, each PV and air conditioner adjusts its own output to solve the voltage overlimit problem.

3.2. Objective Function

For nodes where PV and air-conditioning are installed, the target is to determine the minimum compensation payment of regulation in the distribution network, namely, where and are the quantities of PV and air-conditioning, respectively, which are involved in the regulation; and are the compensation price of active and reactive regulations, respectively, of the th PV; and and are the active and reactive regulations, respectively, of the th PV. is the power regulation of the th air-conditioning, and is the compensation price of the th air-conditioning.

3.3. Constraints

On the basis of the objective function, the constraints which need to be satisfied are as follows.

3.3.1. Constraint of the Elimination of Voltage Violation

The elimination of voltage violation can be determined as follows: where is the difference between voltage at the th node and 1.0 p.u.; is the number of nodes in the distribution network; and are the nodes involved in active and reactive power regulations, respectively; is the active sensitivity of the th node related to the th node; is the reactive sensitivity of the th node related to the nth node; is the active regulation of the th node; is the reactive regulation of the th node; and is the maximum voltage deviation allowed during voltage controlling, which can be determined according to the actual voltage level and voltage regulation requirements. This constraint means that the voltage is within the range of p.u. to p.u. after regulation.

3.3.2. Upper Bound of Power Regulation

For each PV generation, we have

Namely, solar power should not only meet the upper bound of the active and reactive power output but also meet the constraint of the power factor.

For each air-conditioning load, we have which means that air-conditioning only needs to meet the upper bound of the active power.

3.3.3. Constraint of Users’ Comfort

For each air-conditioning load, it should also be that in the regulation process, the indoor temperature does not exceed upper and lower temperature limits that are defined by the users. Accordingly, we have

4. Case Study

In order to verify the effectiveness of the proposed strategy, this section makes a simulation analysis under the IEEE 33-node distribution system, as shown in Figure 4.

The 33-node test system was built in the DigSILENT/PowerFactory simulation platform; 5 nodes are chosen from the 33 nodes to install photovoltaic panels and another 5 nodes are placed with air-conditioning loads. The user type and voltage sensitivity of each node are shown in Table 1. Assume that the outdoor temperature is 34°C and the indoor temperature is 26°C. The maximum temperature, minimum temperature, and expected temperature designated by air-conditioning users are 26°C, 18°C, and 22°C, respectively. The air-conditioning load of each node is initially operated with a minimum power to maintain the room temperature not more than 26°C. The air-conditioning user benefit coefficient , the PV panel user benefit coefficient , and the maximum of permissible voltage deviation . The operating and maintaining costs of the PV active power and reactive power adjustment are $0.0008 per kW·h and $0.0014 per kvar·h, respectively [15].

Taking some node voltage of the 33-node main feeder is overlimited as a consequence of the excess of photovoltaic power at some time. Since the main feeder is a chain structure, making reactive power compensation at the end of the feeder is the most effective [16]. Therefore, considering voltage sensitivities of the nodes where the PV and air conditioners are located at the number 17 node at the end of the main feeder, this section analyzes the optimal results. Through online power flow calculation, the voltage sensitivities mentioned above can be achieved. The calculation result is shown in Table 1.

4.1. Result of Control of Voltage beyond Limits

We adopt the control strategy proposed in this paper and use the voltage regulating equipment at each node to adjust the main feeder voltage. A comparison of the raw and the adjusted voltage is shown in Figure 4.

Due to the excess of photovoltaic power, without adopting the proposed strategy, voltage goes beyond the limit at nodes 11–17 in Figure 5. The voltage limit violation is the most serious at the number 17 node, where the voltage has approached 1.083 p.u. That is why we need to take drastic measures to ensure that the voltage at each node of the distribution network meets the operational requirements. In the strategy adopted, the voltage at each node is regulated within an allowable range of 0.97 p.u. to 1.03 p.u., where voltage overlimit constraints can be eliminated.

The amount of power adjustment of each user is shown in Table 2. Voltage sensitivity of the number 7, number 11, number 17, and number 32 nodes is high. And the PV reactive power output of these four nodes reached the upper limit of the reactive power output limited with the power factor constraints. For the sake of lower voltage sensitivity, the 19th node has pool regulation effects and will not be involved in the voltage regulation. The active power sensitivity of the 15th node is the most visible. The remaining power is assumed by increasing the output of the air-conditioning at the 15th node to meet the regulatory requirement. As a result, the rest of the air-conditioning was loaded only with the minimum power to maintain the indoor temperature to meet user comfort constraints, being unnecessary in participating in the regulation. Besides, PV panels can maintain the current generation power instead of curtailing PV power to control voltage.

In summary, the proposed strategy can not only solve the problem of distribution network voltage beyond the limit but also avoid the curtailment of PV power.

4.2. Economic Analysis

The compensation price for participants in the regulation is shown in Table 3.

The duration time of regulation is 5 min. We figure out that the cost of the compensation is $2.3538. Making full use of the reactive power regulation, the cost of which is low, minimizes the use of PV power curtailment which is expensive. Thus, this strategy can reach the minimum cost of compensation paid by the grid. Minimizing the use of PV power curtailment achieves the PV power accommodation maximization.

When the regulation ends, the air-conditioning load of the number 15 node involved in this regulation turns off and the room temperature recovers naturally. According to (4) and (5), it takes 10 min to recover from room temperature to 26°C. In order to highlight the effect of the control strategy, the following 2 control schemes are used for comparison. In case 1, we adopt the strategy proposed in this paper. In case 2, without using the proposed strategy, we maintain the room temperature at 26°C. Considering the payment of electricity and the variation of temperature, we compare case 1 with case 2. The electricity price is $0.0783/kW·h which is an experienced value based on the electricity price in China.

As is shown in Table 4, even if the air-conditioning is turned off when the regulation ends, the temperature in the room will not rise quickly in a short period of time. It is because the buildings can store heat. The consumption is very low for the duration. Therefore, the total electricity consumption is maintained regardless of the increase in temporary consumption. Besides, users participating in the regulation can gain compensation from the grid company, so the users actually can reduce the electricity payment. It can be seen that the regulation and control proposed will not cause any damage to users’ economic interests.

To summarize, the proposed strategy can effectively solve the voltage beyond the limit and has high economic efficiency.

5. Conclusions

This paper presents a distribution network voltage control strategy based on the coordinated optimization of PV and air-conditioning. The result of the case study shows that the strategy can optimize and allocate the adjustment amount of each PV and air-conditioning according to the sensitivity and the adjustment-compensation bid models. Users who are located in highly sensitive nodes and have lower compensation price participate in the arrangement preferentially, so that the grid can take the optimal control effect with the lowest payment. The adjustment-compensation bid models are submitted by PV and air-conditioning users themselves, which ensures the interest of each user. In addition, air-conditioning users can keep the indoor temperature with lower power after the arrangement, and the waste of the photovoltaic power can be reduced or even avoided. The investment of reactive compensation equipment can be saved to a certain degree as well. As a result, the benefits of all the PV generators, the air-conditioning loads, and the grid are guaranteed.

The presented strategy can be promoted to the coordinated optimization of different kinds of loads and power sources to solve problems like voltage drop caused by the loss of active power. This makes contributions to restraining the fluctuation of renewable power and improving the penetration of distributed generations.

Considering that the output of PV and air-conditioning is time-variant, models reflecting the impact of response characteristics accurately and strategies based on the output characteristics of different loads and generators deserve further research.