Multiple DGs for Reducing Total Power Losses in Radial Distribution Systems Using Hybrid WOA-SSA Algorithm

Table 6

Performance of WOA-SSA compared with those of the standard case without a DG unit, RLF method, WOA, and SSA on an IEEE 123-bus RDN with a single DG.

ParticularsBase case without DGAlgorithms
RLFWOASSAWOA-SSA

Optimal location67676767
Optimal DG size (kW)1978.5952020.4562017.7291979
Total power losses (kW)95.43470.1770.59870.24670.17
% power loss reduction26.5%26%26.4%26.5%
Minimum voltage (p.u.), bus0.98401, 650.97884, 650.97173, 650.97824, 650.97884, 65
Maximum voltage (p.u.), bus1.0481, 831.047, 831.0477, 831.0477, 831.047, 83
Mean voltage (p.u.)1.02071.01711.01861.01731.0171
Standard deviation voltage (p.u.)0.0184160.0164180.0189710.0165460.01642
Computational time (S)90156230256161