Multiple DGs for Reducing Total Power Losses in Radial Distribution Systems Using Hybrid WOA-SSA Algorithm

Table 7

Performance of WOA-SSA compared with those of the WOA and SSA algorithms and the IEEE case without DG on an IEEE 123-bus RDN with multiple DGs.

DG no.ParticularsBase case without DGAlgorithms
WOASSAWOA-SSA

3Candidate buses90, 28, 160149, 56, 97152, 45, 67
Optimal DG size (kW)5000
3822.095
1826.522
755.84
1558.834
1667
1745.644
2642.309
1995.555
Total DG size (kW)10648.6173981.6746383.508
Total power losses (kW)95.43470.69670.97870.292
% power loss reduction25.9%25.6%26.4%
Minimum voltage (p.u.), Bus0.98401, 650.98791, 650.98948, 650.97858, 65
Maximum voltage (p.u.), Bus1.0481, 831.0463, 831.0476, 831.0403, 83
Mean voltage (p.u.)1.02071.02091.02091.0152
Standard deviation voltage (p.u.)0.0184160.0141410.0150430.014254
Computational time (S)231224228

4Candidate buses52, 51, 25, 5452, 42, 250, 5413, 51, 36, 57
Optimal DG size (kW)4491.045
2109.597
2126.813
2034.666
1657.875
2089.409
3275.819
2146.397
488.383
1160.717
2568.928
2479.022
Total DG size (kW)10762.1219169.56697.05
Total losses (kW)95.43474.23873.96973.091
% loss reduction22.2%22.5%23.4%
Minimum voltage (p.u.), bus0.98401, 650.98234, 650.98097, 650.97407, 65
Maximum voltage (p.u.), bus1.0481, 831.0446, 831.0436, 831.0458, 83
Mean voltage (p.u.)1.02071.01351.0131.0123
Standard deviation voltage (p.u.)0.0184160.0190120.018250.017625
Computational time (S)278284274

5Candidate buses81, 48, 149, 23, 6755, 26, 56, 40, 5778, 98, 61, 29, 67
Optimal DG size (kW)2686.689
2003.240
2039.694
1336.645
1770.532
38.473
589.953
4572.243
397.187
2016.337
1599.443
3560.55
1557.516
4062.252
1899.762
Total DG size (kW)9836.87614.19312679.523
Total power losses (kW)95.43470.63572.92870.184
% power loss reduction26%23.6%26.5%
Minimum voltage (p.u.), bus0.98401, 650.97585, 650.98545, 650.97991, 65
Maximum voltage (p.u.), bus1.0481, 831.0412, 831.0468, 831.0453, 83
Mean voltage (p.u.)1.02071.01171.01711.0159
Standard deviation voltage (p.u.)0.0184160.0168130.0164080.015152
Computational time (S)237255232

6Candidate buses26, 28, 13, 10, 51, 538, 9, 35, 42, 250, 53150, 35, 54, 13, 54, 54
Optimal DG size (kW)2457.965
2806.089
1605.001
1912.286
2838.475
2261.193
4565.555
258.574
1393.951
3839.614
1837.754
2789.804
4447.936
322.867
1040.216
191.239
2731.592
2236.8
Total DG size (kW)13881.00914685.25210970.65
Total losses (kW)95.43474.06173.93773.419
% loss reduction22.4%22.5%23.1%
Minimum voltage (p.u.), bus0.98401, 650.98132, 650.97656, 650.98629, 65
Maximum voltage (p.u.), bus1.0481, 831.0432, 831.042, 831.045, 83
Mean voltage (p.u.)1.02071.01311.01191.0169
Standard deviation voltage (p.u.)0.0184160.0180870.0169470.015978
Computational time (S)301302273

7Candidate buses36, 97, 75, 104, 53, 34, 7236, 25, 50, 27, 57, 8, 6753, 56, 42, 64, 51, 62, 67
Optimal DG size (kW)2391.085
5000
2797.53
3450.195
5000
4439.535
1888.471
1
1
5000
1748.772
1
5000
1877.048
1966.79
2039.543
2147.753
3201.916
3603.024
1561.412
1926.957
Total DG size (kW)24966.81613628.8216447.395
Total power losses (kW)95.43471.37670.59770.273
% power loss reduction25.2%26%26.4%
Minimum voltage (p.u.), bus0.98401, 650.97374, 650.97372, 650.97935, 65
Maximum voltage (p.u.), bus1.0481, 831.0479, 831.0448, 831.0458, 83
Mean voltage (p.u.)1.02071.01241.01311.0169
Standard deviation voltage (p.u.)0.0184160.0178360.0183250.016181
Computational time (S)238264233

8Candidate buses36, 26, 27, 30, 29, 22, 37, 1348, 21, 7, 51, 23, 7, 47, 5752, 8, 20, 29, 150, 30, 1, 52
Optimal DG size (kW)2845.921
3590.8
3277.099
1528.684
1221.43
2044.885
2279.321
2862.69
3731.289
2207.028
4943.676
1137.604
2771.666
2076.816
1761.434
2869.06
1217.977
1733.92
2376.75
181.628
2300.277
3794.711
3728.088
2376.548
Total DG size (kW)19650.8321498.57317709.899
Total losses (kW)95.43474.85674.36374.071
% loss reduction21.6%22.1%22.4%
Minimum voltage (p.u.), bus0.98401, 650.99074, 650.96968, 650.9891, 65
Maximum voltage (p.u.), bus1.0481, 831.0465, 831.0443, 831.0485, 83
Mean voltage (p.u.)1.02071.01591.01391.0175
Standard deviation voltage (p.u.)0.0184160.0153190.0189160.016697
Computational time (S)285274275

9Candidate buses23, 250, 49, 35, 18, 2, 17, 37, 5229, 25, 54, 40, 250, 52, 149, 151, 5717, 55, 2, 27, 44, 49, 44, 250, 57
Optimal DG size (kW)1041.278
3539.659
1006.816
1515.389
427.404
467.085
434.462
479.55
2200.006
4370.94
4105.06
4354.954
5000
2044.157
4093.852
3826.531
638.685
2427.329
2445.393
1150.91
68.636
2389.231
3098.096
2860.186
122.912
2677.014
2278.389
Total DG size (kW)11111.64930861.50817090.767
Total losses (kW)95.43474.8672.80572.576
% loss reduction21.6%23.7%24%
Minimum voltage (p.u.), bus0.98401, 650.98417, 650.98069, 650.98257, 65
Maximum voltage (p.u.), bus1.0481, 831.0465, 831.0455, 831.0436, 83
Mean voltage (p.u.)1.02071.01281.01781.0164
Standard deviation voltage (p.u.)0.0184160.0181690.0168010.015684
Computational time (S)278279276