COP calculations of four refrigerants at different storage temperatures.

RefrigerantsR22R134aR404AR717Average value

Design storage temperature (4°C); evaporation temperature (−6°C)3.523.313.063.933.46
Design storage temperature (−5°C); evaporation temperature (−10°C)3.122.872.713.343.01
Design storage temperature (−18°C); evaporation temperature (−28°C)1.64/1.851.741.74
Design storage temperature (−25°C); evaporation temperature (−35°C)1.37/1.471.421.42

The abovementioned data are calculated according to the enthalpy and entropy of refrigerant under different evaporation temperature, suction pressure, condensation temperature, and hydraulic pressure. 2.R134a is not applicable in the low-temperature zone.