Abstract

This paper comparatively studies on the end winding electromagnetic force and mechanical response for generators with different numbers of poles. The analytical expression of the end winding electromagnetic force is derived under the rotor winding interturn short circuit (RISC) considering the pole number. Meanwhile, the three-dimensional transient finite element simulation is carried on two generators with one-pair poles and three-pair poles. Then, the frequency composition and amplitude variation characteristics of the radial, axial, and tangential electromagnetic forces are analyzed. Further, the maximum stress and deformation on the end winding are calculated and the similarity and difference of the coil failure law are obtained for two kinds of generators. It is found that RISC will bring odd harmonics to electromagnetic force for one-pair pole generators but it will bring odd and fraction harmonics for multipair pole generators. Moreover, the max mechanical response under RISC will decrease for one-pair pole generators but it will increase for multipair pole generators.

1. Introduction

The generator is mainly composed of stator, rotor, and auxiliary components. When the rotor rotates, a changing magnetic field will be formed and the electromotive force and current will be excited on the stator winding. Further, the stator winding will generate alternating electromagnetic force under the action of field and current. The stator end winding is suspended outside the stator core, and alternating stress and vibration will be produced by electromagnetic force. Then, fatigue damage of the wire rod and insulation wear will be brought [1]. Due to the interturn insulation damage caused by the poor manufacturing process or copper wire structure defects, fatigue damage, or insulation aging caused by mechanical stress, the rotor interturn short circuit (RISC) occurs very easily. It is an electrical fault with high frequency in the actual working process of the generator. Such fault will not seriously affect the operation of the unit when they are slight in the early stage, and the generator can work with it. But it will cause abnormal distribution of the air gap magnetic field [2], further affect the electromagnetic force and mechanical response of end winding, and aggravate the fatigue damage and vibration wear of some windings. Therefore, it is of great academic and practical significance to analyze the generator end winding electromagnetic force and mechanical response characteristics before and after RISC, so as to obtain the corresponding laws of winding fatigue failure and insulation wear. The study result can provide a basis for winding failure prevention and wear monitoring.

Reference [3] made an online detection of end leakage flux, and it is found that new frequency components will appear in the air gap magnetic motive force (MMF) when the generator is under RISC. Based on this principle, Yuguang et al. invented a new detection coil for the identification of interturn short circuit fault. When RISC happens, the detection coil port voltage appears even or fractional harmonics. However, when the stator interturn short circuit (SISC) happens, the port voltage only contains odd harmonics [4]. The change of air gap MMF under RISC will cause the frequency change of magnetic pull force on the rotor surface, which is related to the stator current frequency and the pole number [5]. In addition, the difference between the actual generator electromagnetic power and the calculated virtual work value will increase with the occurrence of RICS [6]. Hongsen found that the average electromagnetic torque of the rotor will decrease when SISC happens [7]. Therefore, references [811] propose a composite diagnosis method based on stator and rotor vibration characteristics to determine the position and degree of RISC.

Moreover, the change of the air gap magnetic field will further affect the electromagnetic force of end winding. Reference [12] found that RISC will increase the amplitude of the odd harmonic component of stator winding electromagnetic force. This conclusion ignores the influence of the pole number on the reverse MMF, so its application is limited. Reference [13] took a generator with 3 pairs of poles as the object and proposed that the stress and deformation of some end windings decrease after RISC but the change is not obvious, so it does not have sufficient representation.

As an improvement, this paper mainly studies on the electromagnetic force and maximum mechanical response of the end winding before and after RISC and analyses the similarity and difference of generators with different numbers of poles. The remainder of this paper is constructed as follows. The qualitative equation of the end winding electromagnetic force under RISC is derived in Section 2. Then, the finite element analysis of the electromagnetic force and mechanical response are carried out in Section 3 and Section 4. Finally, the main conclusions are drawn up in Section 5.

2. Theoretic Analysis

2.1. Magnetic Flux Density (MFD) Analysis

In the normal condition, the MMF of the stator and rotor windings can be written as [14] where is the circumferential position, is the number of pole pair, is the internal power angle of the generator, is the angle velocity of the rotor, is the electricity frequency (), and and are the th harmonic amplitude of the stator and rotor winding MMF, respectively.

When the RISC happens, the shorted turns will produce a reverse MMF. The shorted position is defined as as shown in Figure 1, and . According to the magnetic flux conservation law, the distribution of reverse MMF is shown in Figure 2 and it can be expressed as where and are the current and number of shorted turns, respectively.

In the light of [13], the reverse MMF can be described as where the absolution of represents the ()th harmonic amplitude of reverse MMF.

Because the rotor MMF is the main part, the influence of RISC on the stator MMF can be neglected. Therefore, the air gap MMF after RISC can be written as where is the th harmonic amplitude of the summed MMF under RISC and is the angle between the summed MMF and rotor MMF vector. The relationship of the fundamental harmonic MMF vectors is shown in Figure 3.

It can be indicated in equation (4) that the time component of rotating frequency is brought to the MMF under RISC and they are the ()th harmonics. Moreover, RISC will result in the variation of the original odd harmonic amplitude and the changing tendency is decided by the pole number, shorted position, and order number (see equation (3)). Because , is constant, that is to say, . So, the fundamental harmonic amplitude of the summed MMF will be decreased and this conclusion is independent of the pole number.

Since RISC mainly affects the MMF and has little effect on the air gap magnetic permeance, the air-gap MFD at the iron core can be obtained by multiplying the RISC MMF and the normal permeance. where refers to the normal permeance (, where and are the vacuum permeability and normal air gap length, respectively).

As indicated in equation (5), it is evident that the MFD change tendency is consistent with MMF under RISC. The fundamental harmonic amplitude will decrease, and time components of rotating frequency will be brought. As shown in Table 1, the MFD mainly contains odd harmonic components such as , , , and so on in normal condition. For a generator with one pair of poles, even harmonics will appear under RISC, such as , , and . For the generator with 3 pairs of poles, fractional and even harmonic components will be added, such as , , , , and .

2.2. Electromagnetic Force Analysis

The main MFD can be achieved by the multiplication of rotor MMF and permeance.

According the electromagnetic induction rule, the stator current can be described as where is the th harmonic amplitude of stator current and is ()th harmonic amplitude. is the effective axial length of the winding, is the velocity that the coil bar cuts the magnetic flux lines, is the impedance of the winding, is the slot number per phase, is the turn number per coil, and is the winding factor of the th harmonic (for details, see [14]).

Through the ampere force law, the electromagnetic force of end coil point K can be expressed as where , , and are rectangular coordinate components of electromagnetic force under RISC. is the circumferential angle of the upper layer line part in the th stator slot, and refers to the position of the point as shown in Figure 4(a). is the angle between the magnetic flux density and the stator current at point , and is the MFD modification coefficient.

Through coordinate transformation and integral calculation, the radial, tangential, axial electromagnetic force components, and resultant force of the end winding under composite fault can be obtained by where is the vector angle of the cylinder coordinate of point and is the coil curve of the end winding.

According to equation (8), in addition to components, the electromagnetic force contains other time components of rotating frequency after RISC. As shown in Table 1, the electromagnetic force in normal condition mainly contains even harmonics such as , , and . When RISC occurs, odd harmonics will appear for the generator with one pair of poles, such as , , and . But fractional and odd harmonic components will be added for the generator with 3 pairs of poles, such as , , , , and .

On the other hand, in RISC condition, the original even harmonic amplitude of will change and the tendency is related with the reverse MMF. Because exists for the fundamental harmonic of reverse MMF and the summed MMF will decrease (see equation (4) and Figure 3, ), therefore the component (that is, the second harmonic) amplitude will decrease. This conclusion has no relationship with the pole number.

3. Study Object and Simulation Settings

In this paper, the electromagnetic force and mechanical response of end winding in the QFSN-600-2YHG turbogenerator and MJF-30-6 fault simulator are simulated by the finite element method. The two objects have one pair of poles and three pairs of poles respectively. The main parameters can be found in references [13, 14], and the layout of windings is shown in Figures 4(a) and 4(b).

During the simulation, for the QFSN-600-2YHG turbogenerator, the rotor excitation current is set as a rated value of 4128 A, the rotor speed is set as a synchronous speed of 3000 rpm, the step length is 0.0005 s, and the simulation time is set as 0.12 s (that is, 6 cycles for the rotor). For the MJF-30-6 fault simulator, the rotor excitation current is set to the rated value of 1.8 A, the rotor speed is set to 1000 rpm, the step size is set to 0.001 s, and the simulation calculation time is 0.36 s (that is, also 6 cycles for the rotor).

4. Simulation Result

4.1. MFD Result
4.1.1. QFSN-600-2YHG Turbogenerator (, )

The radial MFD wave and spectrum at 0° before and after RISC are shown in Figure 5. It can be seen in Figure 5(a) that the MFD matches approximately with cosine. After RISC, it decreases significantly at the peak and the change at the valley is not obvious. This result is similar to the MMF (see Figure 2(a)).

Moreover, it indicates in Figure 5(b) that the MFD includes the obvious 50 Hz (fundamental harmonic ), 150 Hz, and 250 Hz (that is, and ) components. Meantime, the amplitude increases at 100 Hz (that is, ) after RISC and it decreases at 50 Hz. This conclusion is consistent with the theoretical analysis result of equation (5).

4.1.2. MJF-30-6 Fault Simulator (, , )

The radial MFD wave and spectrum at 0° are shown in Figure 6. It shows in Figure 6(a) that, after RISC, the MFD decreases obviously at the no. 2 peak, increases slightly at the no. 1 and no. 3 peaks, and decreases slightly at the three valleys. So, the variation law is similar to MMF in Figure 2(b).

Further, it can be seen in Figure 6(b) that the magnetic density includes the obvious 50 Hz (fundamental harmonic ), 150 Hz, and 250 Hz (that is, and ) components. At the same time, the amplitude at 50 Hz decreases after RISC and it increase at 16.7 Hz, 33.4 Hz, 66.7 Hz (that is, , , and ), and so on. These results reflect the correction of theoretic equation (5).

4.2. Electromagnetic Force Result

The frequency components of electromagnetic force are shown in Figure 7 () and Figure 8 (). Here, is the number of pole pairs.

4.2.1. QFSN-600-2YHG Turbogenerator (, )

The electromagnetic force of each end coil can be obtained through finite element analysis. Taking phase A coils as an example, the electromagnetic force of coil 7 is the largest and its force spectrum before and after RISC is shown in Figure 7. It can be seen from the comparison that, in addition to the obvious DC constant, harmonics at 100 Hz and 200 Hz (that is, and ), there is a weak harmonic at 150 Hz () after RISC. This is consistent with the conclusion in theoretical analysis equation (8).

Because the second harmonics is the most obvious, its amplitude for 42 end coils is shown in Figure 9. It is shown that the force amplitude of coils 60° apart is still approximately equal and the amplitude of interphase coils is the largest. However, the second harmonic amplitude of electromagnetic force decreases after RISC. Accordingly, the vibration wear of the coil at second harmonic will also be reduced.

4.2.2. MJF-30-6 Fault Simulator (, , )

The electromagnetic force of coil 2 is the largest in the phase A coils, and its force spectrum before and after RISC is shown in Figure 8. It indicates that there are obvious DC constants and 100 Hz (that is, second harmonic) components. After RISC, weak components at 16.7 Hz, 33.3 Hz, and 50 Hz (that is, , , and ) increase and the harmonic amplitude at 100 Hz decreases from 9.25 mN to 8.91 mN. It well verified the theoretic equation (8).

In summary, the second harmonic amplitude of electromagnetic force decreases after RISC, as shown in Figure 9 () and Figure 8 (). And this conclusion has no relationship with the pole number.

4.3. Mechanical Response Result

Through the finite element calculation of the mechanical structure, the maximum stress and deformation of each coil of phase A are obtained. The response of the no. 1 coil is the largest for the QFSN-600-2YHG turbogenerator, and the no. 3 coil is the largest for the MJF-30-6 fault simulator. Therefore, these two coils are selected as representation to analyze the response characteristics.

4.3.1. Equivalent Stress

The maximum stress distribution of end winding for the QFSN-600-2YHG turbogenerator and MJF-30-6 fault simulator is shown in Figure 10. It indicates that the max stress occurs on the root part and the nose part also has a larger stress. Moreover, the max stress is reduced from 132 MPa to 110 MPa after RISC for the QFSN-600-2YHG turbogenerator (see Figures 10(a) and 10(b)) but it is increased from  Pa to  Pa for the MJF-30-6 fault simulator (see Figures 10(c) and 10(d)). This result is related to the change of MFD. The max value of MFD decreases for the QFSN-600-2YHG turbogenerator and increases for the MJF-30-6 fault simulator as shown in Figures 5(a) and 6(a).

4.3.2. Total Deformation

The maximum deformation distribution of end winding for the QFSN-600-2YHG turbogenerator and MJF-30-6 fault simulator is exhibited in Figure 11. It shows that the max deformation on the nose part is the largest. In the meantime, the max deformation decreases from 1.39 mm to 1.01 mm after RISC for the QFSN-600-2YHG turbogenerator (see Figures 11(a) and 11(b)) but it increases from  m to 1.47 m for the MJF-30-6 fault simulator (see Figures 11(c) and 11(d)). And the reason is the same as the above stress change.

5. Conclusion

In this paper, the electromagnetic force and mechanical response of stator end winding are comparatively analyzed for two generators with one pair of poles and 3 pairs of poles, respectively. It is found that RISC can decrease the second harmonic (that is, 100 Hz) amplitude of the electromagnetic force and this conclusion has no relationship with the pole number. In the meantime, odd harmonics (that is, 50 Hz, 150 Hz, and so on) will be brought to electromagnetic force after RISC for one-pair pole generators but the new components are odd and fraction harmonics (16.7 Hz, 33.3 Hz, and 50 Hz, for example) for 3-pair pole generators. Moreover, the max stress and deformation under RISC will decrease for one-pair pole generators and increase for 3-pair pole generators. So the RISC is more dangerous for multipair generator winding damage. The conclusions can lay a foundation for the reverse suppression of end winding fatigue failure and insulation wear.