Abstract

This paper presents experiments and measurements on a low speed permanent magnet cable wound generator for marine current energy conversion. Measurements were made for no load and nominal load (4.44 Ω/phase) conditions at nominal speed (10 rpm). For either load condition, the magnetic fields in the air gap were also measured. The measurements on the generator were compared with the corresponding finite element method simulations used to design the machine. It is shown in the paper that measurements and corresponding case simulations show good agreement. At nominal speed, the measured and simulated load voltages (nominal load) differ less than 1% for the rms values and less than 5% for peak values. At no load, measured and simulated voltages had larger differences, that is, <9% for rms values and <5% for peak values. Harmonic analyses of measured and simulated phase voltages and currents show only the presence of third harmonics. The percentage of harmonics in the measured data was comparable with the corresponding predictions of the simulations. The discussions and results presented in the paper could be beneficial for future design of efficient and reliable marine current energy converter systems.

1. Introduction

For energy resources such as wind, wave, and tidal power, it may be beneficial to adapt the generators to the nature of the resource. For wind and wave power, several generator designs have been presented by both industry and academia [19]. So far, published material concerning generators designed specifically to match the tidal current regime have been less abundant. However, in recent years interesting generator topologies suited for marine current turbines have been suggested in literature, for example [912]. Authors of this paper have previously discussed the advantages of having a variable speed permanent magnet (PM) direct drive generator for extracting energy from tidal and marine currents and presented simulations, for example [13]. Some of the main design objectives were to achieve a high efficiency at low speeds to exclude the use of a gearbox, and to maintain a low load angle to allow for electrical control and breaking of the turbine at high flow velocities.

To study the electrical performance of such a low speed machine, a prototype generator with nominal ratings 5 kW, 150 V, 10 rpm, and 10 Hz was designed and constructed for laboratory tests, see Figure 1 and Table 1. A thorough presentation of the electrical and mechanical design of the generator can be found in [14]. The experimental results presented here validate the simulations previously presented in [13, 14]. The generator is designed for a system with a vertical axis turbine with fixed blade pitch and a directly driven generator [15]. This requires a generator that can be efficiently operated at different speeds and loads.

In this paper, results from no load and nominal load operation are presented. Voltages and currents are measured, as well the magnetic field in the air gap. These measurements form a reference for comparisons with the corresponding finite element method (FEM) simulations used for the initial design of the generator [14]. Simulations of the generator performance at variable speed operation are also presented to highlight its ability to electrically control and brake the turbine at high flow velocities that can occur in rivers or tidal currents. Such electrical power control is intended to replace mechanical systems for power control, such as blade pitch mechanisms and mechanical brakes.

The load tests were carried out primarily to evaluate the performance of the machine under nominal load conditions. Harmonic analyses of the measured data are presented and possible reasons for the electromagnetic losses and harmonics in the experimental machine are discussed. The results and discussions presented in the paper could be useful for future design and construction of generators for marine current energy conversion.

2. Finite Element Generator Model

For electromagnetic analysis and design of electrical machines, FEM has emerged as more or less a standard tool. The generator presented in this paper has been analyzed in the finite element environment ACE (ACE, Modified Version 3.1, ABB common platform for field analysis and simulations, ABB Corporate Research Centre, ABB AB, Corporate Research, 721 78 Västerås, Sweden), based on a two dimensional field model of an axial cross-section of the generator.

After the generator geometry is decided, the different subdomains of the calculation geometry are allocated material properties such as electric conductivity, 𝜎, and relative magnetic permeability, 𝜇𝑟. Nonlinear ferromagnetic material properties of the stator steel are represented by a single-valued BH curve. Three-dimensional end effects are taken into account by introducing coil end impedances in the circuit equations of the stator windings and the permanent magnets are modeled by surface current sources.

Rotating machines usually present symmetry conditions that allow for a reduction of the necessary calculation geometry. In this case, a fractional winding with 7/5 slots per pole and phase is used, and thus the calculation geometry includes a section of five poles and 21 stator slots (see Figure 2).

The complete generator model is described by a combined set of field and circuit equations. The magnetic vector potential inside the generator is described by 𝜎𝜕𝐴𝑧1𝜕𝑡+𝜇0𝜇𝑟𝐴𝑧=𝜎𝜕𝑉𝜕𝑧,(1) where 𝜎 is the conductivity, 𝜇 is the permeability, 𝐴𝑧 is the axial component of the magnetic vector potential, and 𝑉 is the applied potential (thus the right hand term denotes the applied current density).

The circuit equations are described by 𝐼𝑎+𝐼𝑏+𝐼𝑐𝑈=0,(2)𝑎𝑏=𝑈𝑎+𝑅𝑠𝐼𝑎+𝐿end𝑠𝜕𝐼𝑎𝜕𝑡𝑈𝑏𝑅𝑠𝐼𝑏𝐿end𝑠𝜕𝐼𝑏,𝑈𝜕𝑡(3)𝑐𝑏=𝑈𝑐+𝑅𝑠𝐼𝑐+𝐿end𝑠𝜕𝐼𝑐𝜕𝑡𝑈𝑏𝑅𝑠𝐼𝑏𝐿end𝑠𝜕𝐼𝑏,𝜕𝑡(4) where 𝐼𝑎, 𝐼𝑏, and 𝐼𝑐 are the conductor currents in the three phases 𝑎, 𝑏, and 𝑐, respectively. 𝑈𝑎𝑏 and 𝑈𝑐𝑏 are the terminal line voltages and 𝑈𝑎, 𝑈𝑏, and 𝑈𝑐 are the phase voltages obtained from solving the field equation. 𝑅𝑠 is the winding resistance and 𝐿end𝑠 describes the coil end inductance. Furthermore, it should be noted that frictional losses in the bearings and windage losses are neglected while evaluating the efficiency due to the low rotational speed and high torque.

3. Generator Parameters

Before performing the tests on the machine, some of the electrical circuit parameters and geometrical parameters of the experimental machine were measured under standstill conditions. The resistance and inductance per phase of the winding is 0.475 Ω and 11.5 mH. These values were measured using a precision bridge [16]. For a full description of the generator geometry, see [14].

A fractional winding is used and the number of slots per pole per phase is 1.4, hence the angular displacement between the slots is 𝛽=42.8 and the phase spread angle is 60°. Hence, the distribution factor is 𝑘𝑑=0.977. In the present case the pole pitch is 4.2 slots. The designed machine is short pitched by 35.5° and the pitch factor is 𝑘𝑝=0.952.

For safety, and to avoid possible floating conditions of either generator or the load, the neutral of both the generator and the load are shorted and grounded to the common power supply ground of the motor drive unit. Both the generator and the loads are Y connected.

4. Generator Performance

4.1. No Load Experiments

The generator no load test was carried out at the nominal speed of 10 rpm. Once the generator had reached a constant speed, the magnetic field in the air gap was measured on a stator tooth using a 7010 Gauss/Tesla meter [17], that is, the Hall probe was fixed at one stator tooth perpendicular to the magnetic flux. Note that there are two components of magnetic fields in the air gap, namely, normal, 𝐵𝑛, and tangential, 𝐵𝑡, components. Only the normal component was measured by the Hall probe. The simulated value for the 𝐵-field is taken at a point 1 mm in front of a stator tooth as shown in Figure 2, to match the position of the Hall probe during measurements. Also shown in Figure 2 are the magnetic field lines in one section of the machine. The measured normal component of the no load air gap magnetic fields is shown in Figure 3 together with the magnetic field predicted by the simulations. Simulations show that the maximum normal component and tangential components of the magnetic field in the air gap are around 0.6 T and 0.15 T, respectively. The difference in the peak normal component of the measured and calculated magnetic fields is about 6%. The force per unit area in the air gap at no load is calculated to 65 kN/m2 using the simulation tool.

The no load phase voltages were measured for all three phases and they all were balanced and phase shifted by 120°. Hence only the voltage for one phase is shown in Figure 4 together with the voltage predicted by the simulations. The differences in the rms value of simulated and measured voltages are shown in Table 2. It is found that the rms value of the simulated voltages are about 9% higher when compared with the measurements. This is most likely due to measurement uncertainties and modeling inaccuracies regarding for example end effects. Furthermore, the small differences in axial length of the rotor and the stator due to constructional errors are not taken into account in the modeling of the generator. The voltages were measured using three Tektronix P2220 voltage probes [18].

4.2. Nominal Load Experiments

The generator load tests were carried out at the nominal speed of 10 rpm and with a Y connected load of 4.44 Ω/phase. The magnetic field was measured in the same way as in the no load test case. The measured normal component of the magnetic field is shown in Figure 5. Also shown in Figure 5 are the magnetic fields in the air gap predicted by the simulations under the same load conditions on the designed generator at a point 1 mm in front of the stator tooth.

It is found that the calculated maximum normal and tangential components of the magnetic field in the air gap are around 0.6 T and 0.04 T, respectively. As far as the differences in the magnetic fields under no load and load conditions are concerned, it is seen that the normal component of the magnetic field is not significantly affected by either load conditions at nominal speeds. The force per unit area in the air gap at nominal load operation is about 63 kN/m2 according to simulations.

The phase voltages and phase currents measured under load conditions are shown in Figures 6 and 7, respectively, together with corresponding values predicted by simulations. The differences in the rms value of simulated and measured voltages and currents are shown in Table 3. From the data in Figure 6, it is found that the differences between the simulated and the measured rms voltages at nominal load are less than 1%. However, from Figure 7 it is seen that the differences between the simulated and measured rms currents are around 4%. The currents were measured using a universal power clamp Metrix MX240 [19]. A four channel Lecroy Wavesurfer 424oscilloscope [20] was used for all the voltage and current measurements.

To quantify the harmonic contents in the machine, the measured voltages and currents were Fourier transformed. The measurements were made at sampling frequencies greater than ten times the highest harmonic (the 5th) found in the simulations. Only the fundamental and third harmonic components are seen in the measured nominal load currents and voltages. The simulations predict a negligible fifth harmonic as well. In terms of percentage, the third harmonic in the measured current and voltage at nominal load is 2%, while the simulations predict 6%. Table 4 shows the harmonic content in the phase voltage at nominal load and no load conditions.

The differences in the measured and simulated harmonics could be due to constructional and modeling inaccuracies or differences. It is preferable to keep the harmonics in the machine low as they cause additional losses in the machine core and in the copper. Moreover, in the future this type of generator will be connected to a rectifier. The role of harmonics for variable speed operation of a synchronous generator connected to a diode rectifier is further discussed in [21].

The power delivered to the nominal load at 10 rpm is about 4.7 kW (see Figure 8). The electromagnetic losses in the generator from the simulations are presented in Table 5. The copper losses from the measured currents and resistances are about 0.5 kW and agree well with simulations. The simulations predict an efficiency of about 86% at nominal conditions for this generator.

4.3. Simulation of Variable Speed Operation

In order to show the generator's ability to control and brake the turbine at the different flow velocities that can occur in rivers or tidal currents, the efficiency of the generator at variable speed has been simulated and is shown in Figure 9 for nominal load and a load of 0.5 pu. It can be seen that the designed machine’s efficiency is in the range of 78%–88% in the speed range of 4–20 rpm. Since the differences in the simulations and measurements for the cases discussed earlier are small, the actual efficiency of the experimental generator can be expected to be in the same range. That would allow for electrical control of the turbine while maintaining a good working efficiency. As a comparison, simulations of the line voltage drop and efficiency at nominal speed and varying load is shown in Figure 10. It can be seen that the armature reaction is low and that the generator can be used to control the turbine with only a small decrease in efficiency.

In the actual marine environment the efficiency of the total system depends on the power coefficient 𝐶𝑝 of the turbine. The anticipated control of the system is to keep a fixed tip speed ratio (TSR), hence keeping the optimum 𝐶𝑝 for the turbine without exceeding the cavitation limits by controlling the generator load. At higher velocities, the generator will keep the turbine at a lower TSR (and thus lower 𝐶𝑝) to limit the power absorbed by the turbine. Hence the generator will be run at both varying speeds and loads to control the TSR of the turbine. This control strategy has been effectively implemented in the case of wind power systems [22, 23].

Another important design criterion is the capacity of the generator to efficiently brake the turbine in the intended range of operation to exclude the use of blade pitch and mechanical brakes. To illustrate this, the generator has been simulated with a resistive dump load of 1.5 Ω and compared to the power delivered from a hypothetical vertical axis turbine (𝐶𝑝 of 0.35, delivering 5 kW at 10 rpm in a water current of 1.5 m/s) running at a fixed TSR at increasing water velocities, see Figure 11. It can be seen that the generator safely brakes the turbine at velocities up to twice the nominal speed.

5. Conclusions

In this paper the electrical tests on a 5 kW, 10 rpm, permanent magnet cable wound direct drive generator for marine current energy conversion are presented. No load and nominal load tests were compared with the corresponding finite element simulations using the designed generator. In both tests, the magnetic field distributions in the air gap were also compared. It is found that the differences between the experiments and calculations are less than 10%. Harmonic analyses show the presence of 2% third harmonic content. The efficiency of the designed machine is 78%–88% in the speed range of 4–20 rpm according to simulations. The low armature reaction and high overload capability show that the generator can be used to electrically control and brake the turbine in the intended range of operation.

Acknowledgments

Dr. Arne Wolfbrandt and Dr. Karl-Erik Karlsson are hereby acknowledged for development of the simulation tool. Sincere thanks to Ulf Ring for supervision and assistance during the construction work. Special thanks to Dr. Nelson Theethayi for interesting discussions, support, and encouragement during the time of writing. The experimental setup was funded by Vattenfall AB and the Swedish Centre for Renewable Electric Energy Conversion (financed by Uppsala University, The Swedish Agency for Innovation Systems (VINNOVA) and The Swedish Energy Agency (STEM)). The authors would also like to acknowledge the Swedish Research Council (grant no. 621-2009-4946).