Modeling Electromechanical Overcurrent Relays Using Singular Value Decomposition

Table 8

Comparison of results by ANFIS and SVD for the CRP9 relay.

TopANFISErr1Err1%SVDErrErr%


413521368161.181352.000.000.00
860560940.66605.000.000.00
1245945630.65459.000.000.00
1637537410.27375.000.000.00
2035835620.56358.000.000.00

AV = 5.2AV% = 1.59AV = 0.00AV% = 0.00


424592477180.732459.000.000.00
811531132211.821153.000.000.00
12894883111.23894.000.000.00
1674473950.67744.000.000.00
2066966540.60669.000.000.00

AV = 11.8AV% = 0.61AV = 0.00AV% = 0.00


439353963280.713935.000.000.00
817541738160.911754.000.000.00
121304130510.081304.000.000.00
161123112410.091123.000.000.00
201024102730.291024.000.000.00

AV = 9.8AV% = 0.64AV = 0.00AV% = 0.00

M: multiples of tap value current; TDS: time dial setting; top: actual operating time in milliseconds; ANFIS: fitted value by adaptive network and fuzzy inference system; Err1: absolute value of difference between top and ANFIS value; Err1%: absolute value of difference between top and ANFIS in percentage; SVD: fitted value by singular value decomposition; Err: absolute value of difference between top and SVD value; Err%: absolute value of difference between top and SVD value in percentage; AV: average of absolute values of errors in milliseconds; AV%: average of absolute values of percentage errors; refer to [9].