Protection for DC Distribution System with Distributed Generator
Table 2
The setting values of parameters (sampling frequency of protection device: 5 kHz).
| Protection types | Parameters | Setting values |
| Start component | Protection startup setting value | (kV) | 0.1 | DC bus protection | Differential current setting value | (kA) | 0.5 | DC line protection | | | | Line 1 (CB2, CB4) | Instantaneous current setting value | (kA) | 2.5 | Time-limit current setting value | (kA) | 0.6 | Delay setting value | (s) | 0.1 | Reverse current margin | (kA) | 0.05 | Line 2 (CB5) | Instantaneous current setting value | (kA) | 1.3 | Time-limit current setting value | (kA) | 0.7 | Delay setting value | (s) | 0.1 | Line 3 (CB6) | Instantaneous current setting value | (kA) | 1.2 | Time-limit current setting value | (kA) | 0.7 | Delay setting value | (s) | 0.1 | Line 4 (CB7) | Instantaneous current setting value | (kA) | 1.4 | Time-limit current setting value | (kA) | 0.7 | Delay setting value | (s) | 0.1 | The outlet of rectifier (CB3) | Reverse current margin | (kA) | 0.05 |
|
|