Reliability Assessment of Active Distribution System Using Monte Carlo Simulation Method
Table 1
Impacts of substation capacity.
| Charge and discharge strategy | Substation capacity (MW) | LOLE | LOEE | SAIFI | SAIDI | EENS |
| Load-following | 13 | 0 | 0 | 1.3815 | 6.6364 | 32.671 | 11 | 9.3812 | 3.4664 | 1.3965 | 6.7033 | 32.968 | 9 | 212.24 | 156.94 | 1.3971 | 6.7549 | 33.223 | 7 | 849.61 | 1174.6 | 1.3999 | 6.7548 | 33.259 | 5 | 2128 | 3932.2 | 1.5 | 7.9927 | 38.353 | 3 | 5010.5 | 10653 | 1.7695 | 10.0764 | 47.568 | 1 | 8069 | 24362 | 2.1862 | 12.9036 | 60.861 |
| Cycle charge | 13 | 0 | 0 | 1.1001 | 5.0396 | 24.621 | 11 | 0.7126 | 0.2931 | 1.1125 | 5.0485 | 24.804 | 9 | 20.43 | 14.24 | 1.1138 | 5.0589 | 24.873 | 7 | 163.79 | 260.84 | 1.1347 | 5.2858 | 25.751 | 5 | 989.89 | 2268.3 | 1.2073 | 5.7744 | 28.048 | 3 | 3913.2 | 9145 | 1.4518 | 7.7969 | 36.992 | 1 | 7910.8 | 24161 | 2.0388 | 12.1559 | 57.085 |
|
|