Research Article

A Real-Time Embedded Control System for Electro-Fused Magnesia Furnace

Table 1

Inputs and outputs of the controller.

Signal typeA/D; I/ODetails

3-phase electrode currentsAnalog; 3-channel input0~20 mA
3-phase electrode voltages Analog; 3-channel input0~20 mA
3-way raw weight valueAnalog; 3-channel input0~20 mA
Furnace rotation speedAnalog; 1-channel input0~20 mA
Speed value set by the manual resistorAnalog; 1-channel input0~20 mA
4-way inverter rotation speedAnalog; 4-channel output0~20 mA
Upper and lower limit switch of 3-phase electrode Digital; 6-channel inputSwitch signal
Loosen signal of 3-phase electrode holderDigital; 3-channel inputSwitch signal
Holding signal of 3-phase electrode holderDigital; 3-channel inputSwitch signal
High temperature of hydraulic oil Digital; 1-channel inputSwitch signal
Low temperature of hydraulic oilDigital; 1-channel inputSwitch signal
Filter clogging in hydraulic stationDigital; 1-channel inputSwitch signal
High pressure of cooling waterDigital; 1-channel inputSwitch signal
High temperature of cooling waterDigital; 1-channel inputSwitch signal
The furnace reset in place Digital; 1-channel inputSwitch signal
Automatic control markDigital; 1-channel inputSwitch signal
Manual control markDigital; 1-channel inputSwitch signal
Manual control electrode liftdigital; 6-channel inputSwitch signal
Exhaust buttonDigital; 1-channel inputSwitch signal
Electric vibrator start buttonDigital; 1-channel inputSwitch signal
Electric vibrator stop buttonDigital; 1-channel inputSwitch signal
Inverter forward/stopDigital; 4-channel outputSwitch signal
Inverter reverse/stopDigital; 4-channel outputSwitch signal
Electric feeder machine start/stopDigital; 1-channel outputSwitch signal