Management of Voltage Profile and Power Loss Minimization in a Grid-Connected Microgrid System Using Fuzzy-Based STATCOM Controller

Table 2

Power flow results of voltage in IEEE 30-bus system including microgrid and STATCOM controller.

Voltage magnitude in per unit
BusesBase caseWith MGWith MG & FACTS

Bus 11.061.061.06
Bus 21.0431.0431.043
Bus 31.01090261.0068181.009946
Bus 41.00005390.995180.998932
Bus 5111
Bus 61.000400240.9947880.99947
Bus 70.991874220.9884750.99947
Bus 81.011.010.99104
Bus 91.005169371.0034271.01
Bus 10111.004794
Bus 11111
Bus 121.006819841.0034271
Bus 1310.9875130.993152
Bus 140.991242290.9807870.988467
Bus 150.986544620.9948280.996998
Bus 160.996371520.9928230.993503
Bus 170.993328950.9747210.979772
Bus 180.97850840.9744570.977923
Bus 190.977056530.9800060.982618
Bus 200.981964940.9882660.992154
Bus 210.990710040.9855270.991603
Bus 220.989544120.9606670.978467
Bus 230.973958930.9430030.974167
Bus 240.966019390.8735220.965257
Bus 250.940692830.8527890.946585
Bus 260.921511290.8412860.969968
Bus 270.934224920.9815430.997718
Bus 280.99828650.7219930.934573
Bus 290.884594860.649920.954784
Bus 300.883415690.659941.009995
Bus 310.6689091.009995
Bus 320.6685081.009954
Bus 330.6689181.01