Management of Voltage Profile and Power Loss Minimization in a Grid-Connected Microgrid System Using Fuzzy-Based STATCOM Controller
Table 3
Total generation, power consumption, and total power losses in the IEEE 30-bus test system with and without microgrid and FACTS.
| Voltage magnitude in per unit | IEEE 30-bus system | Base case (p.u.) | With MG (p.u.) | With MG & FACTS (p.u.) |
| Total generation real power (p.u.) | 12.8056 | 13.236 | 13.23677 | Total generation reactive power (p.u.) | 2.87686 | 3.292914 | 3.197345 | Total load real power (p.u.) | 12.51 | 12.99579 | 13.0362281 | Total load reactive power (p.u.) | 2.73345 | 2.779339 | 2.7999962 | Total loss real power (p.u.) | 0.29560 | 0.397967 | 0.359338 | Total loss reactive power (p.u.) | 0.14340 | 0.245767 | 0.129539 |
|
|