Research Article
Implementation of Optimal Protection Coordination for Microgrids with Distributed Generations Using Quaternary Protection Scheme
Table 10
Dual-directional primary and backup relay operating times for quaternary scheme in grid-connected microgrid.
| DG operating status | Fault location | Operating times (t) of relay in second (Rp = primary relay; Rb = backup relay) | Rp | Rb1 | Rb2 |
| Status 1 | F-1 | R1 | R6 | R5 | 0.099 | 0.399 | 0.410 | R2 | R3 | R4 | 0.163 | 0.453 | 0.466 | F-2 | R3 | R2 | R1 | 0.139 | 0.440 | 0.454 | R4 | R5 | R6 | 0.099 | 0.408 | 0.421 | F-3 | R5 | R4 | R3 | 0.119 | 0.425 | 0.440 | R6 | R1 | R2 | 0.124 | 0.466 | 0.475 |
| Status 2 | F-1 | R1 | R6 | R5 | 0.099 | 0.405 | 0.418 | R2 | R3 | R4 | 0.157 | 0.473 | 0.492 | F-2 | R3 | R2 | R1 | 0.146 | 0.450 | 0.463 | R4 | R5 | R6 | 0.099 | 0.393 | 0.412 | F-3 | R5 | R4 | R3 | 0.099 | 0.394 | 0.404 | R6 | R1 | R2 | 0.126 | 0.580 | 0.601 |
| Status 3 | F-1 | R1 | R6 | R5 | 0.104 | 0.412 | 0.425 | R2 | R3 | R4 | 0.167 | 0.468 | 0.472 | F-2 | R3 | R2 | R1 | 0.153 | 0.461 | 0.478 | R4 | R5 | R6 | 0.099 | 0.404 | 0.417 | F-3 | R5 | R4 | R3 | 0.102 | 0.448 | 0.466 | R6 | R1 | R2 | 0.129 | 0.461 | 0.474 |
|
|