Static Voltage Stability Assessment of the Kenyan Power Network

Table 8

Voltage stability margins of the selected load buses in critical Q-Modes after removal of the line.

Q-modeBUSActive power voltage stability marginPercentage decrease in VSM (P)Active power voltage stability marginPercentage decrease in VSM (Q)

1Maungu0.39092.49570.46901.0448
Titanium0.38721.15390.41781.2521
Manyani0.39281.37670.46711.0422
Vipingo0.41021.98100.48551.0282
MSA cement0.49231.04680.48891.0548
Kilifi0.58071.48910.57160.8878
Jomvu0.43131.38360.42571.2681
Voi0.47520.77720.51370.9416
New Maungu0.52390.83510.53890.9003

2Ndhiwa0.46900.16780.51340.1712
Awendo0.48330.47550.53700.1626
Kisii0.46070.06920.50620.0578
Chemosit10.39670.86790.43590.2398
Chemosit20.34350.44330.37160.2578
Bomet0.47170.79800.51900.2084

3Sultan Hamud0.38081.18340.46880.9786
Mtito Andei0.38651.22350.46351.0400
Wote0.51040.34200.54080.9347
Ulu0.41100.84280.47970.9300
New Sultan Hamud0.55720.59980.58050.8938
Kiboko0.54640.92050.56080.9140

4Lokichar0.40950.06570.45600.0746
Kalemngorok0.44300.05350.51860.0463

5Garissa0.52150.32370.55390.3056
Mwingi0.52070.20870.56940.3353