Research Article
Power Consumption: Base Stations of Telecommunication in Sahel Zone of Cameroon: Typology Based on the Power Consumption—Model and Energy Savings
Table 2
Equipment of the FM room.
| Equipment | Power | Other characteristics and working hours |
| 2 FM TX 10 KW (national program and local program) | 2 × 22.5 KVA | Working 24 h/24; frequencies of emission: 98.10 MHz for FM National and 94.80 MHz for FM Regional | Dummy load | 1 KVA | Working 24 h/24 | PIE RACK | 1 KVA | Working 24 h/24 | Measuring equipment | 1 KVA | Working 24 h/24 | Dehydrator | 1,5 KVA | Serial number: 35651, Sumiden Opcom, Ltd, NP: 1604, working 24 h/24 | Two air conditioners | 2 × 12 KVA | Working 24 h/24, adjusted at 19°C | Spare | 0,5 KVA | Working 24 h/24 | Transformer isolator | 80 KVA | Working 24 h/24 | Voltage regulator | 75 KVA | AVR and PDB, work 24 h/24 | Two lighting lamps | 2 × 36 W | Working 24 h/24 |
|
|