Power Consumption: Base Stations of Telecommunication in Sahel Zone of Cameroon: Typology Based on the Power Consumption—Model and Energy Savings
Table 4
Equipment of MTN Missinguileo site.
Equipment
Electrical characteristics
Other characteristics
AES-Sonel supply
Amperage 10–30 A, voltage 220 V/400 V, Power supplied: 15 kVa
Couple C = 2,5 wh/tr
2 TX/RX 900 GSM (DRU) et TX/RX 1800 GSM (DRU)
Max 3600 W × 3 Supply 48 V DC
ERICSON 02G 89450736652; work at 24 h/24
Energy bay Emerson Network Power (charger of batteries made of rectifiers AC/DC)
Redresseurs 220 V–24 V Puissance minimale 10 KW
Works 24 h/24
Eight accumulator batteries
Power sonic PG-6V 220B; 6 volts 226 A.H
6 V-200 A; autonomy 8 h; temperature 27°C.
Power system ERICSON
DC output: 24 V ou 48 V DC/200A/6,4 KW
Works 24 h/24
Standby generating set
Apparent power 20 KVA; power factor 0.8; output 16 KW
Works automatically in case of AES-Sonel power cut
Two air conditioning systems
Cooling input power: 2410 W Rated voltage: 220 V–230 V
Only one system works and is adjusted at 23°C, 24 h/24. The second is under failure
Five buoying lamps of red coulor
11 W × 2
220 V-50 Hz, work from 6:00 pm to 6:00 am
Four lighting lamps
36 W × 4
240 V-50 Hz, work at 24 h/24
One radio equipment Airmux 200
Supply 48 V DC 3 W
Serial LIU STM-1/STS-3; E1/T1 way side A B. P1-Direction KATOUAL CH1 P2-Direction KATOUAL CHP
WIMAX equipment
Supply 48 V DC 14 W
Supplies six directorates in internet network: (i) Lycée Kaelé (Centre multimédia) (ii) Camair-co (iii) Régionale AMCHIDI (iv) Direction Sonel Maroua (v) CDC Bomtock (vi) Afriland First Bank Kousseri
Multiplexer OSN 2500 Digital multiplexer 2/34
400 W 15 W
Of trademark HUAWEI, work 24 h/24 SMU 16 × 2; MMU 34 + 2