Research Article

A New Algorithm for the Available Transfer Capability Determination

Table 4

Results of point-to-point ATC for the 39-New England bus system.

Point of transfersLimiting lineATC (MW)CPU Time (minute) Number of load flow solutions
Selling busBuying busRalston’s with cubic-splineRecursive AC power flowRalston’s with cubic-splineRecursive AC power flowRalston’s with cubic-splineRecursive AC power flow

30162–302362350.030.6018235
302019-201281270.030.3218127
3032–302332330.030.5818233
32312-1348470.030.121847
322412-1341400.030.101840
322712-1344440.030.111844
3333–181281280.030.3218128
332416–242912910.030.7318291
332717–272932920.030.7418292
34414-151311300.030.3318130
34253–181961950.030.4818195
342617–273533520.030.8518352
3533–181271270.030.3218127
351515-161451450.030.3618145
352716–212682670.030.6518267
361214-151171170.030.2918117
362816–213293290.030.8018329
3633–181271270.030.3118127
371512-131861860.030.4618186
372412-132412410.030.6018241
372625-262432430.030.6018243
3833–181741730.030.4318173
38829–381761760.030.4418176
382429–381761760.030.4418176
392112-131031020.030.2618102
392212-131021020.030.2718102
392412-131031020.030.3518102