Radial Basis Function Neural Network Application to Measurement and Control of Shunt Reactor Overvoltages Based on Analytical Rules

Table 1

Effect of switching time and remanent flux on the maximum of overvoltages and duration of 𝑉 p e a k > 1.3 p.u.

Switching angle (deg.)Remanent flux ( p.u. ) 𝑉 p e a k   (p.u.)Duration of ( 𝑉 p e a k > 1.3 p.u.) (s)

200.271.92050.5628
200.651.58410.3394
750.271.65370.3064
600.51.52930.2675