Abstract

Accurate modeling of Kaplan turbine regulating system is of great significance for grid security and stability analysis. In this paper, Kaplan turbine regulating system model is divided into the governor system model, the blade control system model, and the turbine and water diversion system model. The Kaplan turbine has its particularity, and the on-cam relationship between the wicket gate opening and the runner blade angle under a certain water head on the whole range was obtained by high-order curve fitting method. Progressively the linearized Kaplan turbine model, improved ideal Kaplan turbine model, and nonlinear Kaplan turbine model were developed. The nonlinear Kaplan turbine model considered the correction function of the blade angle on the turbine power, thereby improving the model simulation accuracy. The model parameters were calculated or obtained by the improved particle swarm optimization (IPSO) algorithm. For the blade control system model, the default blade servomotor time constant given by value of one simplified the modeling and experimental work. Further studies combined with measured test data verified the established model accuracy and laid a foundation for further research into the influence of Kaplan turbine connecting to the grid.

1. Introduction

Hydraulic turbine generator units are increasingly being relied upon to meet a variety of control requirements as the size and complexity of interconnected systems increase. To establish models reflecting the actual characteristics of the prime mover and its governor is an important foundation work for the accuracy of power grid security and stability analysis [1, 2]. It is necessary to adjust both the wicket gate opening and the runner blade angle under different water head by the governor to keep efficient operation of a Kaplan turbine, which is one of the common forms of turbines in hydropower systems [3, 4]. There is an urgent need to establish Kaplan turbine regulating system dynamic model suitable for power system analysis based on measured experimental data to obtain the parameters [5].

There have been many studies on the modeling and verification of Francis turbine [610]. The common Francis turbine model contains the single regulator system model, the wicket gate control system model, and the turbine and water diversion system model. The ideal turbine model or linearized turbine model reflects the basic characteristics of the prime mover, but the ideal turbine model reflects unit features at rated operating point and the linearized turbine model is suitable for small power fluctuations [8, 9].

The operation of Kaplan turbine involves control of the wicket gates and the runner blades position to regulate the water flow into the turbine [2, 11]. Due to the on-cam relationship between the wicket gate opening and the runner blade angle, the impact of blade angle on Kaplan turbine transient simulation accuracy should not be ignored [12, 13]. The linear fitting [14], polynomial interpolation and fitting [15], or intelligent algorithm [16] was used to obtain the on-cam relationship expression. However, the linear fitting obtained via limited points [14] to an extent may fail to reflect the function completely. Different Kaplan turbine and water diversion system models based on different functions of wicket gate opening multiplied by function of blade angle as inputs of nonlinear turbine model were compared [17]. The parameter identification of a turbine and water diversion system model may become difficult with high-order fitting function of the wicket gate opening or the blade angle. As a result, the applicability of the established model declines.

The Kaplan turbine regulating system model contains the mathematical models of the governor, the dual-regulated vane control system and blade control system, and the turbine and water diversion system. In this paper, the Kaplan turbine regulating system dynamic model and parameters were optimized suitable for power system analysis, experimental measurement, and precision requirements. The main contribution lies in the blade control system model simplification, the on-cam relationship obtainment, the derived five-parameter linearized Kaplan turbine model, parameter obtainment method, and different Kaplan turbine regulating system dynamic models comparison in gird connected system. The structure is organized as follows. In Section 2, the Kaplan turbine regulating system model is presented. Section 3 contains the development of three kinds of Kaplan turbine and water diversion system model (i.e., the linearized Kaplan turbine model, the improved ideal turbine model, and the nonlinear Kaplan turbine model). The established model is verified by comparison with the measured data in Section 4. The results and discussion are presented in Section 4 as well. Section 5 presents the conclusions drawn thereof.

2. Kaplan Turbine Regulating System Mathematical Model

Figure 1 shows the frame diagram of hydroelectric power with double-regulated turbine [18]. The vane control system is based on the same principle of Francis turbine. The on-cam relationship presents the runner blade angle changes with the wicket gate opening and the blade is kept in a certain best angle fitting with the wicket gate opening to improve the power generation efficiency.

and are the unit frequency and given frequency value, respectively, and and are the given power and turbine load, respectively. , , and are the given wicket gate opening, the actual wicket gate opening, and the blade opening, respectively. The blade opening is transferred from the blade angle with the maximum value no more than one. is the turbine working flow, is the turbine working head, and is the mechanical power output.

2.1. The Regulating System Model

The Kaplan turbine governor system is consistent with that of the general Francis turbine. Figure 2 shows the digital governor model. Also, Figure 3 shows the vane control system model considering the speed limit and the amplitude limit [18]. , , and are the proportional, integral, and differential coefficients of the governor, respectively. , , and are the proportional, integral, and differential coefficients of the integrated amplifier module, respectively. is the power deviation magnification. is the main servomotor time constant. and are the open and close servomotor speed limits, respectively. and are the limiting values of the wicket gate opening.

2.2. Blade Control System Model

The principle of the blade control system is similar to that of the vane control system, assuming that the on-cam relationship between the wicket gate opening and the runner blade angle is neglected [19]. The blade control valve adopts a proportional valve to handle the blade servomotor. Figure 4 shows the blade control system model under a certain water head. is the blade servomotor time constant. and are the open and close servomotor speed limits, respectively. and are the limiting values of the blade opening.

The function between the blade opening, the gate opening, and the water head is expressed as

Under a certain water head, the function of the wicket gate opening and the runner blade opening is given bywhere , , , , , and are the fitting coefficients.

3. Kaplan Turbine and Water Diversion System Model

The linearized Kaplan turbine model, improved ideal turbine model, and nonlinear Kaplan turbine model were developed. The five-parameter linearized Kaplan turbine model was derived for parameters obtainment convenience. The improved ideal turbine model and nonlinear turbine model were demonstrated based on the principle of the turbine that the blade opening affected the Kaplan turbine power like the linearized turbine model did.

3.1. Model One: Linearized Kaplan Turbine Model

The dynamic characteristic of hydraulic turbine is associated with the dynamic characteristic of the water flow in the pipe. The turbine characteristics in the vicinity of the operating point are approximately linear. Compared with the Francis turbine [9], the torque and water flow of Kaplan turbine can be expressed as where , , , and are the transfer coefficients of turbine torque to the rotational speed, wicket gate opening, blade opening, and water head, respectively. , , , and are the transfer coefficients of the water flow to the rotational speed, wicket gate opening, blade opening, and water head, respectively.

For the turbine water diversion system, considering the wall elasticity of water flow and water diversion system and ignoring the friction between them, the mathematical model of water diversion system can be obtained as [6]where is the water inertia time constant and is the water hammer phase length.

If the high level terms in the Taylor expression of (4) are ignored, then the transfer function of the simplified elastic model is given as

Furthermore, if the flexibility of the water flow and the water diversion pipe is ignored, the transfer function of the rigid water hammer model is expressed as

The speed influence on the turbine power in (3) is neglected due to the little unit speed change under the grid connected condition. Figure 5 shows the linearized Kaplan turbine model and its deformed five-parameter linearized turbine model with rigid water hammer model, while , , , , and are constants above zero.

3.2. Model Two: Improved Ideal Turbine Model

Assume that the transfer coefficients in (3) and the turbine efficiency are certain under various working conditions and the wicket gate opening varies linearly. Ignoring the unit speed influence on turbine power, the ideal turbine model of the Francis turbine at rated operating point is described as [8]

Figure 6 shows the improved ideal turbine considering the effect of the wicket gate and the blade on Kaplan turbine power. is the equivalent no-load opening. is the proportional coefficient. The blade effect on the Kaplan turbine power is reflected by the calculation of and , which are identified by an optimization algorithm in this paper.

3.3. Model Three: Nonlinear Kaplan Turbine Model

For the Francis turbine, considering the relationship between the turbine flow, wicket gate opening, and the water head as a valve [19], the nonlinear turbine model is described bywhere is the water flow in the diversion pipeline, is the derivative of , is the static head (its per unit value is 1), and is no-load flow. is proportional coefficient.

The nonlinear Kaplan turbine model is established based on the following four aspects:

(a) Under the normal grid connected operation, the unit speed is generally in the vicinity of rated speed, so the unit speed impact on the turbine model is ignored.

(b) The hydraulic turbine with the water diversion pipe length less than 800 m can adopt the rigid water hammer model to simulate the dynamic process of the water diversion pipe.

(c) Consider the nonlinear relationship between the wicket gate opening and the turbine mechanical power.

(d) The effect of the blade opening on the Kaplan turbine is viewed as increasing flow amount.

The variable is introduced to represent the equivalent opening for the combined effect of the wicket gate opening and the blade opening given bywhere and are the function of and , respectively.

Different to the Kaplan turbine and water diversion system models based on concrete different functions of and [17], function is represented by cubic polynomial fitting and function is represented by linear fitting given bywhere , , , and are the fitting coefficients. is the coefficient representing the blade angle impact on the turbine water flow. Herein the effect of the blade opening on the turbine is considered as incremental flow referring to the principle of Kaplan turbine and the parameters in (10) are easy to obtain for engineering application and model validation, which reflects the nonlinear characteristics and working principle of Kaplan turbine.

There is a time delay between the wicket gate movement and the consequent blade angle movement in the case studied. Figure 7 shows the nonlinear Kaplan turbine model with rigid water hammer model considering the above four aspects combined with (8)–(10).

4. Results and Discussion

The testing of the Kaplan turbine regulating system model is based on the Kaplan turbine at Tukahe hydropower plant in Yunnan province of West China. The hydropower station has three units with one unit capacity of 55 MW, normal reservoir storage level of 368 m, and rated head of 25 m.

Different fitting functions of on-cam relationship were compared based on the whole range measured under given wicket gate opening disturbances while the gate-runner relationship was determined from the turbine characteristics (TC) data in [17]. The blade control effect is mainly determined by the on-cam relationship, speed limits, and blade servomotor time constant of the blade control system model. The default blade servomotor time constant given by value of one simplified the modeling and experimental work. The Kaplan turbine regulating system dynamic model and three different turbine and water diversion system models were compared for stability analysis in the grid connected power system.

4.1. On-Cam Relationship Validation of Wicket Gate Opening and Blade Opening

The fifth order polynomial fitting of the on-cam relationship between the wicket gate opening and the blade opening based on the measured data near the rated water head is expressed as

The blade opening is set to a certain value near zero when wicket gate opening is less than 40%. The best fitting function is obtained through measured data depending on different Kaplan turbines or different working heads. The relationship between the wicket gate opening and the blade opening needs to be revised with appropriate polynomial fitting at other working heads. Figure 8(a) shows the simulated blade opening of the blade control system model (see Figure 4) using the expression in (11) under given wicket gate opening disturbances of whole range.

As shown in Figure 8(a), when the wicket gate opening is less than 0.4 by per unit value, the blade opening is approximate to zero and the maximum blade opening is about 0.9 by per unit value. The piecewise linear fitting result fits with the measured data when the wicket gate opening is less than 0.6 and has a difference as the wicket gate opening over 0.6 by per unit value. The fifth order fitting shown in (11) is closest to the measured data which shows a better on-cam relationship than the other fitting methods. Given the wicket gate opening disturbances, the simulation result using fifth order fitting is consistent with the measured data in the whole operating range (see Figure 8(c)) and verifies the correctness of the on-cam relationship function.

4.2. Influence of Blade Servomotor Time Constant on the Blade Control System Model

The influence of blade servomotor time constant on the blade control system model was studied. Figure 9 shows the simulation results with different values.

The influence of different values on the simulation results shows that the bigger is, the slower adjusted rate is (see Figure 9), and thus should be as small as possible. Due to the rate restrictions of and , the result difference is not obvious when is less than 1 s. In conclusion, the blade servomotor time constant affects the adjustment of blade control system model and should be set in a reasonable range of value. in this case is 1 s considering that it is difficult to be tested. When is about 1 s (i.e., the blade servomotor response time link is ignored), it has little effect on the simulation result but simplifies the modeling and experimental work.

4.3. Turbine Regulating System Model Validation

The improved particle swarm optimization (IPSO) algorithm (i.e., the inertia weight is linearly changed and the chaos method is used to generate initial particle population) is applied to identify the model parameters [20]. The inertia weight is introduced to revise the speed update equation to improve search ability in the global scope. The chaos method is used to generate good initial particle population.

The error evaluation index to quantize the simulation agreement is defined as where is th measured value, is th simulation value, and is the total number of sampling points.

Figure 10 shows the graphical representation of measured behavior of power acquired at a certain head given in 2D and 3D space. changes with when the wicket gate opening is over a certain value. In addition, the relationship between the wicket gate opening and the turbine mechanical power is nonlinear.

The speed limits and amplitude limits of the vane control system and blade control system were calculated under large wicket gate opening disturbances while other parameters were identified by the improved particle swarm optimization (IPSO) algorithm under small wicket gate opening disturbances and the parameters were revised through grid connected simulation comparison. The maximum iteration step of IPSO algorithm is 100. For the error function with the extreme point of zero, the tolerance of error is set to 10−6. The parameters generally range from slightly greater than 0 to 100 to get global solution as much as possible. Based on the turbine power disturbance test data and the unit frequency disturbance test data, Table 1 lists the cubic fitting relation between variables and (see Figure 7), the coefficient representing blade angle impact on the turbine water flow, and other parameters of the double regulating system model identified by the IPSO algorithm. Figure 11 shows the Kaplan turbine regulating system model simulation result using nonlinear Kaplan turbine model for unit frequency disturbance test with disturbance values of ±0.2 Hz under a certain unit power value.

From the simulation results shown in Figure 11, the initial recorded gate opening and blade opening are about 0.5 and 0.2 by per unit, respectively. The blade opening changes linearly under the speed limits effect in the model and the blade opening change is slower than the wicket gate opening change which can be seen from Figure 8 and speed limit differences listed in Table 1. There is little difference at the final mechanical power value due to measured blade opening difference when the unit frequency is recovered to 50 Hz. The wicket gate opening response and the blade opening response results agree with the measured curve indicating that the established vane and blade control model can effectively reflect the dynamic characteristics of Kaplan turbine.

Table 2 shows the identified parameters of the Kaplan turbine and water diversion system model using model one and model two.

Figure 12 shows the comparison results of the turbine power rising test using these three turbine models (i.e., model one, model two, and model three) and decreasing disturbance test using model three with the same Kaplan turbine regulating system mathematical model, respectively. Also, Table 3 lists the power rising disturbance simulation errors of three models.

The Kaplan turbine and water diversion system model using model one (i.e., the linearized Kaplan turbine model) to a certain extent does not accurately reflect the hydroturbine dynamic process when the power output is between 0.62 and 0.72 by per unit value (see Figure 12). As shown in Table 3, model two failed to completely reflect dynamic change of the blade opening and its simulation result has a significant difference with the measured curve. The output of model three (i.e., the nonlinear Kaplan turbine model) is basically the same with the measured curve which is more accurate than model two. In summary, model one and model three apply dual input of the wicket gate opening and the blade opening. These two models regard the effect of blade opening on Kaplan turbine as increasing flow amount and, as a result, influence the unit power output. Through verification of the frequency disturbance test and turbine power disturbance test, the nonlinear Kaplan turbine model can meet the needs of the Kaplan turbine dynamic simulation better.

The generator rotor inertia time constant is obtained by load rejection test. Figure 13 shows the measured curves and the speed fitting result under load rejection of 25 MW.

The rotor motion equation is given bywhere is the rotor inertia time constant. and are the rotor acceleration and rotor mechanical torque change by per unit value, respectively. The calculated rotor inertia time constant from linear segment of the speed change between 1 and 2 (see Figure 13(b)) is 5.3 s.

4.4. Grid Connected Simulation Analysis of Kaplan Turbine

The Kaplan turbine regulating system model was established and the simulation was performed on the IEEE 39-bus system [21] with three different kinds of Kaplan turbine and water diversion system models using model one, model two, and model three in Section 3 and the same Kaplan turbine regulating system mathematical model in Section 2, respectively. The Kaplan turbine is connected to bus 18. Figure 14 shows the revised 39-bus system diagram.

The generator parameters of bus 40 herein are as follows: , , , , , and , and the rotor inertia time constant of the generator is 6 s while the other parameters in the system are not modified.

Assume that there is a three-phase short-circuit fault on lines 17-18 near bus 18 at 1 s, and lines 17-18 are disconnected at 1.1 s. Figure 15 shows the simulation results.

As shown in Figure 15, the terminal voltage of Kaplan turbine is rapidly reduced to around zero when a three-phase short-circuit fault occurs. Each observation returns to the steady-state value after removing the fault line besides the reactive power with value of a little increase. The terminal voltage changes with the three kinds of the turbine regulating system dynamic model (i.e., the Kaplan turbine and water diversion system model using model one, model two, and model three) are basically the same. Under the initial turbine mechanical power output of 0.45 (i.e., the mechanical power is 27 MW), the angle speed and the mechanical power fluctuations of model two are larger than those of model one and model three with the maximum deviation being about 0.3 Hz. The maximum mechanical power fluctuation value of model two is about 0.08 by per unit value (the reference capacity of 100 MVA). In addition to different turbine and water diversion system models, the governor parameters (the governor converts the frequency deviation to wicket gate opening) also influence the amount of mechanical power adjustment.

The adjustment of nonlinear turbine model was finer than that of the improved ideal turbine model since the latter was derived based on the linearized model near the rated condition and its transfer function was simple. From the turbine operating characteristics, the coefficients in (3) may change significantly with turbine running in other conditions; thus, the original parameters may cause a large amount of power fluctuation.

5. Conclusion

Kaplan turbine model in this paper is divided into the governor system model, the blade control system model, and the turbine and water diversion system model. The detailed dual-regulated vane control system model and blade control system model were developed. The comparison of simulation and measured results showed the reasonableness and effectiveness of the established model and parameters. The on-cam relationship between the wicket gate opening and the blade opening and the influence of the blade servomotor time constant on the blade control system model were studied. The blade opening was transferred from the blade angle and the fifth order polynomial fitting function could characterize the on-cam relationship with amplitude limits set of the blade opening in this study. The blade servomotor time constant should be set in a reasonable range of value, but it was difficult to be tested. In this study, was 1 s, and thus the blade servomotor response time link could be ignored. However, it had a little effect on the simulation result and simplified the modeling and the experimental work.

Progressively the linearized Kaplan turbine model, improved ideal turbine model, and nonlinear Kaplan turbine model are developed. The nonlinear Kaplan turbine model is proposed which reflects the effects of the wicket gate opening and the blade opening changes on the turbine mechanical power (i.e., it regards the effect of blade opening on Kaplan turbine as increasing flow amount) and has a high accuracy through the comparison of the simulation and the measured results. The power disturbance test and the frequency disturbance test confirmed that the established governor model, the dual-regulated vane and blade control system model, and the nonlinear Kaplan turbine model reflected the dynamic response of the Kaplan turbine adequately, which could be applied in the power system analysis.