Abstract

The high-voltage power transmission tower-line system, which is a high flexible structure, is very susceptible to the wind-induced vibrations. This paper proposes the utilization of the internal resonance feature of the spring pendulum to reduce the wind-induced vibration of a transmission tower. The kinetic expression of the spring pendulum system is obtained through Lagrangian equation. The condition of the internal resonance is verified to be λ = 2, in which λ is the ratio of the spring mode frequency over the pendulum mode frequency. A 55 m tower in the Liaoning province is established in SAP2000 to numerically verify the effectiveness of the proposed device. The spring pendulum is modeled using Link element. The wind speed history is generated based on Kaimal spectrum using harmonic superposition method. Results show that, (1) compared with the suspended mass pendulum, the spring pendulum absorbs more energy and reduces the oscillation more effectively and (2) the vibration control performance of the proposed spring pendulum improves as the external wind load increases.

1. Introduction

The high-voltage transmission tower-line system is a vital facility in the power transmission system. However, the transmission tower-line system generally has low frequencies and damping ratios associated with their fundamental oscillation modes, and when subjected to wind loads, it may experience large amplitudes of oscillation [1]. Recent investigations have reported several tower failures due to strong wind excitations [2, 3]. Failures of the transmission tower-line system may cause massive blackouts, resulting in major direct and indirect consequences on the economy and national security [4]. It is of great importance to reduce the vibrational response and improve the reliability of power transmission towers under wind loads.

During the past two decades, many researchers and engineers have paid much attention to this issue and proposed many techniques to improve the wind-resistance of the transmission towers [5]. Conventional techniques aim at increasing the stiffness of the transmission tower by enlarging the cross-section area of the steel members or shortening the effective member length by adding additional members. These methods will tremendously increase the project cost and thus are not financially acceptable [2]. An alternative approach to prevent the catastrophic damage of transmission tower is to install vibration control devices [5, 6].

The vibration control devices for vibration control of transmission towers can be divided into two categories. One category aims at increasing the damping ratio by incorporating energy dissipating dampers, such as friction-type reinforcing members [2, 7, 8], magnetorheological (MR) dampers [9], viscoelastic dampers (VED) [10], lead viscoelastic dampers (LVED) [11, 12], and giant magnetostrictive material (GMM) actuators [13].

The other category involves attaching a linear dynamic absorber to the tower. Kilroe [14] installed vibration absorbers on members of tower arms to mitigate the fatigue phenomena. Battista et al. [15] proposed a pendulum-like damper, which reached reduction efficiency of over 90% with the first mode of vibration. Liu and Li [16] combined the linear spring model and the Maxwell model to simulate the tuned mass damper (TMD) in a 3D tower model. Numerical results showed that the vibrational response was reduced by 17% with optimal design. He et al. [17] proposed a suspended mass pendulum (SMP) for vibration reduction of a transmission tower. Both numerical and experimental results verified that the SMP was very effective in reducing acceleration of the tower. These absorbers are all linear absorbers. Introducing nonlinearity may improve the vibration control performance.

Recently, nonlinear vibration absorbers have been developed in a related field of vibration control of buildings. The nonlinear attachments can localize the vibration energy in a one-way, irreversible fashion [18, 19]. This phenomenon is called nonlinear energy sink (NES). Compared with the traditional linear dynamic absorber, NES has a wider effective frequency band and better vibration reduction performance [18, 19]. The NES can be achieved in many ways, such as incorporating a nonlinear cubic spring [19], incorporating collisions [20], or incorporating the internal resonance [21].

The spring pendulum (SP) which is basically a mass suspended by a spring can be regarded as a combination of a simple pendulum and a spring oscillator [22, 23]. It has two modes of vibrations, the pendulum mode and the spring mode. When the SP is correctly designed, the two vibration modes will be strongly coupled, and vibration energy can be transmitted between the two modes. This is called internal resonance, and because of this internal resonance feature the SP can be designed as a new type of NES for vibration control of power transmission tower-line systems.

In this paper, the SP is proposed as a new type of NES to improve the wind-resistant performance of the transmission tower-line system. In Section 2, the kinetic expression of the SP will be obtained through Lagrangian equation. The internal resonance feature will be discussed and the optimal design of a SP will be given. In Section 3, a multimass model of a practical transmission tower will be established to numerically verify the effectiveness of the SP. The wind field will be simulated using superposition method based on Kaimal spectrum. The numerical results will be presented in Section 4. Compared with the traditional SMP, the SP absorbs more energy and reduces the oscillation more effectively. Moreover, the intensity of the wind load will be varied to investigate its influence on the vibration control performance in this section.

2. Mechanism of the Spring Pendulum

2.1. Mathematical Model of a SP

As shown in Figure 1, the SP is basically a mass block suspended by a linear spring. The motion equation can be derived through Lagrangian equation. In Figure 1, denotes the stiffness of the spring, is the original length of the spring, is the length under gravity load, and is the mass of the mass block. Therefore,

Establishing a rectangular coordinate at the center of the mass block, and denote the displacements of the mass block in the two directions. Correspondingly, , , , and are the velocity and acceleration. The total kinetic energy and potential energy are

Substitute (2) into the Lagrangian equation, and the motion equation can be obtained as follows:

At any moment, the forces on the mass block in the two directions are

2.2. Internal Resonance Feature of the SP

The SP has two vibration modes: the spring mode and pendulum mode. Define as the ratio of natural frequencies of the two vibrating modes. Considerwhere and are the circular frequencies of the spring mode and pendulum mode.

According to the literature [22], if , the spring mode and the pendulum mode will be strongly coupled and the kinetic energy will be transferred between those two modes. Figure 2 presents the locus diagram of a SP ( kg,  N/m, and  m). The locus diagram agrees well with the results of the literature [22]. As shown in Figure 2, the suspended mass initially swings as a pendulum; the kinetic energy is mostly in the pendulum mode. After several periods, the kinetic energy is transmitted to the spring mode and the vibration of the mass is mostly in the vertical direction like a simple spring-mass oscillator. This phenomenon, which is named internal resonance, can enlarge the energy absorbing ability of the pendulum. Therefore, SP is more effective in reducing the vibration than a regular SMP.

2.3. One DOF Structure Controlled by a SP

Figure 3 shows a one-degree of freedom (DOF) structure controlled by a SP. Its equation of motion can be written as follows:where , , and are the mass, damping, and stiffness of the primary structure, , , and are the acceleration, velocity, and displacement, denotes the loading force, and is the restoring force generated by the SP. can be calculated by (4). Substitute (4) into (6), and (6) can be expressed as follows:whereIt can be easily verified that . Therefore, the SP added a nonlinear spring to the primary structure. This nonlinear spring can reduce the vibration of the primary structure.

The vibration control mechanism of the SP can also be explained in terms of energy. The SP has two vibration modes, the pendulum mode and the spring mode. It can absorb the kinetic energy of the primary structure to the pendulum mode thus reducing the vibration of the primary structure. In this case, the SP works like a regular SMP. Moreover, the kinetic energy of the pendulum mode can also be transmitted into the spring mode. Therefore, the SP has larger energy absorbing ability than the regular SMP and is more effective in vibration control than the SMP.

2.4. Optimal Design of the SP

Two conditions should be satisfied in order to achieve the optimal design of the SP. One condition is that the frequency of the pendulum mode matches the frequency of the primary structure to be controlled; that is, . Here, and are the frequency of the spring pendulum and the primary structure. Since the frequency of the pendulum mode is determined by the length of the spring , should be determined as follows:where is the gravitational acceleration.

The other condition to be satisfied is that . Then (5) can be written as follows:

Therefore,where is the stiffness of the spring, is the mass of the SP, and is the length of the spring.

3. Numerical Model of the Transmission Tower-Line System Controlled by SP

3.1. Prototype and the FEM Model of the Transmission Tower-Line System

In order to verify the vibration control effectiveness of the proposed SP, a practical transmission tower-line system illustrated in Figures 4 and 5 is chosen as the primary structure to be controlled. The tangent tower is constructed of Q345 angle steels. Its height is 53.9 m. The power transmission tower-line system includes three towers and four span lines as shown in Figure 4. The distance between adjacent towers is 400 m. The upper 8 cables are ground lines and lower 24 cables are four-bundled conductor lines. The properties of the conductor line and ground line properties are listed in Table 1.

The transmission tower-line system is established in a FEM software, SAP2000. The angle steels of the tower and the isolators are modeled using Beam element; the conductor/ground lines are modeled using Cable element. The base points of the transmission tower are fixed on the ground. The connections between transmission towers and lines are hinged.

3.2. Modeling the SP in SAP2000

The SP is simulated by Link element in SAP2000, as shown in Figure 6. Length and stiffness of the Link element are calculated using (9) and (11). One joint of the Link element is hinged to the tower to be controlled. Mass of the SP is assigned to the other joint of the Link element. Figure 7 shows the locus of a spring pendulum calculated by SAP2000. The curve attained by SAP2000 is in good accordance with the theoretical results. Therefore, the Link element can be used to simulate the behavior of the SP.

3.3. Simulation of Wind Field

In wind engineering, the total wind velocity can be simulated as the sum of the mean velocity and the fluctuating wind velocity:where is the total wind velocity, is the mean wind velocity, and denotes the fluctuating wind velocity.

According to the statistic data, the mean wind is often expressed by logarithmic function or exponent function associated with the height [24]:where is the mean wind speed of height , is Karman constant, is the ground roughness length, and is friction velocity.

The time history of the fluctuating wind can be regarded as a random process with a specific power spectrum. According to the theory presented by Shinozuka and Jan [25], the fluctuating wind can be simulated using harmony superposition method:where is the time history of the fluctuating wind. is the frequency increment calculated by , in which denotes the division number and is the cut-off frequency of calculation. is obtained from Cholescky decomposition of the wind cross-spectral density matrix; is the phase angle of structure between the two different load points; denotes the random phase distributed in the range of .

Based on the central limitation theorem, the random process will gradually tend to be the Gauss process when . And the time interval should meet the requirement of [26]. In this paper, they are selected as , , and . The target power spectrum is Kaimal fluctuating wind power spectrum.

In order to study the influence of the wind load intensity on the vibration control performance of the SP, the mean wind velocity at the height of 10 meters above the ground is selected as 20 m/s, 30 m/s, and 40 m/s.

Because the transmission tower nodes are numerous, it is difficult to simulate the wind velocity history for every node of the tower. Consequently, the transmission tower is simplified by 15 regions as shown in Figure 8. The wind load acts only on the center of each region. The position of each region center and windward area are listed in Table 2. Similarly, each cable is divided into 10 segments. Wind load only acts on the middle of each segment. Figure 9 shows the wind speed on the top of Tower 2 at  m/s case. Figure 10 compares the target wind power spectrum and the simulated time history of the fluctuating wind. As shown in Figure 10, the simulation results agree well with the target spectrum.

3.4. Damping Consideration

Determination of the damping ratio of the power transmission tower-line system is a sophisticated problem. Damping ratio of the steel structure is usually valued 2% [27]. Moreover, the aerodynamic damping of the conductor has a significant effect on the dynamic performance [28]. According to the theory presented by Gani and Légeron [29], the aerodynamic damping can be calculated with the following equation:where is the aerodynamic damping, is the intensity of air, is the drag coefficients, is the mean wind speed at height , and is the area exposed to wind loading.

4. Effectiveness of Vibration Reduction

4.1. Criteria to Evaluate Vibration Control Performance

In order to verify the effectiveness of the proposed device, a SP and a SMP of the same mass ratio are designed to compare their vibration control effectiveness. Here, the mass ratio is defined as follows:where is the mass ratio, is the mass of the vibration control device, and is the mass of the power transmission tower. In this paper is selected to be 2%.

To evaluate the vibration control effectiveness of the SP and the SMP, the vibration reduction ratio is defined as follows:where is the vibration reduction ratio and and are the response of the tower with and without vibration control devices. and can be the maximum value or the root mean square value (RMS). The maximum value can be calculated with the following equation [28, 30]:where is the peak dynamic response, is the mean or time average response, is the RMS of the fluctuating response, and is the gust response factor, generally in the range of 3-4 [28].

4.2. Comparison of Vibration Reduction Performance

Based on the numerical model and the simulated wind field, dynamic response of the power transmission tower-line system can be calculated. The time step is chosen as 0.05 s. Figures 1113 show the results of the  m/s case. Results of  m/s case and  m/s case are very similar to that of the  m/s case. Therefore, the figures of those two cases are omitted in this paper. The vibration reduction ratios of those two cases can be found in Table 3.

Figures 11 and 12 compare the displacement and acceleration at the top of Tower 2 from 450 s to 500 s in the  m/s case. Figure 13 shows the envelopes of displacements, accelerations, and internal forces of Tower 2. It is clear that SP is more effective than the SMP. The SP effectively reduced the RMS value of the displacement and acceleration by 36.1% and 30.2% whereas that of the SMP is only 28.6% and 18.4%, respectively. The proposed SP mitigated the maximum displacement of Tower 2 by 15.1%, larger than that of the SMP, which is only 12.1%. In terms of acceleration, greater effective mitigation is achieved by the SP having the maximum value reduced by 19.3%. The reduction ratio of the SMP is only 13.8%. In terms of axial internal force, greater effective performance has also been observed with the SP. In Figure 13(c), the largest axial internal force is reduced by the SP by 20.2%, which is also larger than the reduction ratio of SMP which is 11.0%.

4.3. Influence of the Wind Speed on the Vibration Reduction Performance

The SP is essentially a nonlinear damper. Thus its vibration control performance may be influenced by the intensity of external loads. Table 3 lists the vibration reduction ratio of the SP under 3 cases, namely, the  m/s case, the  m/s case, and the  m/s case. It is clear from Table 3 that the vibration performance is influenced by the level of wind loads. As the wind speed increases, the vibration reduction ratio of the SP also increases, which implies that the SP is more effective under strong winds.

This phenomenon may be explained this way: at low wind speed, the vibration of the transmission tower is small. Therefore, the SP absorbs little kinetic energy from the transmission tower and its motion is very small. The vibration of the SP is mostly in the pendulum mode. Figure 14(a) shows the locus of the SP in the  m/s. As can be seen, the SP vibrates like a linear SMP. Therefore, its vibration reduction ratio is close to that of the SMP. As the wind speed increases, the SP will vibrate more severely as it absorbs more energy. Figure 14(b) corresponds to the case of  m/s. As can be seen, the motion of the SP is larger than that of the  m/s case, and the locus is no longer similar to that of the SMP. This implies that more energy is transmitted to the spring mode of the SP. The vibration absorbing ability is improved by the internal resonance feature.

5. Conclusion

This paper proposed to utilize the internal resonance feature of the SP in order to reduce the wind-induced vibration of the power transmission tower-line system. The motion equation of the spring pendulum system was obtained through Lagrangian equation. A practical transmission tower-line system was established in SAP2000 to assist numerical study. An SP and an SMP with the same mass ratio were designed to compare the vibration control performance. Based on theoretical analysis and numerical results, the following conclusions are drawn:(1)The condition of internal resonance is verified to be . When this condition is satisfied, the pendulum mode and the spring mode of the SP will be strongly coupled and the vibration energy will be transmitted from the pendulum mode to spring mode. Consequently, the SP has larger vibration absorbing ability than the regular SMP and is more effective in reducing the vibration of the primary structure.(2)The proposed SP can be simulated using the Link element in SAP2000. The numerical results calculated by SAP2000 agree well with the theoretical results.(3)The numerical study verified that the SP showed better vibration control performance than the regular SMP.(4)The vibration control performance of the SP is influenced by the wind load. The SP works like a regular SMP and its vibration reduction ratio is small at low wind speed. As the wind speed increases, the internal resonance feature of the SP becomes more obvious and the vibration reduction ratio increases. This implies that the SP is more effective under larger wind loads.

Conflict of Interests

The authors declare that there is no conflict of interests regarding the publication of this paper.

Acknowledgment

This research work was supported by the Science Fund for Creative Research Groups of the National Natural Science Foundation of China (Grant no. 51121005).

Supplementary Materials

The spring pendulum is basically a mass block suspended by a spring. It has two motions: the spring motion and the pendulum motion. Those two motions can be strongly coupled. The gif on the left shows the motion of a spring pendulum. The other gif shows its motion calculated by Matlab.