Research Article
Control Strategy of Three-Phase Photovoltaic Inverter under Low-Voltage Ride-Through Condition
Table 1
Parameters of photovoltaic inverter system.
| Category | Name |
Parameter |
| System parameters | Maximum DC voltage |
1000 | Maximum DC power | 560 kWp | DC voltage range with MPPT | 480~880 | Maximum current output | 1167 A | Startup DC voltage | 520 | Rated power output | 500 kW | Rated grid voltage | 315 | Total harmonic distortion of current | <2% (rated power output) | DC component of current | <0.5% (rated current output) |
| Filter parameters | Inductance value of | 100 uH | Inductance value of | 50 uH | Capacitance values for | 200 uF (Δ-connected) | The resonant frequency of LCL | 1125 Hz |
| Other parameters | Capacitance values for | 25.12 mF | Switch frequency of IGBT | 3000 Hz | Sample frequency | 10000 Hz |
|
|