Tab 2
/
Research Article
A Novel Protection Scheme against Fault Resistance for AC Microgrid
Table 2
Active power values and the protection threshold setting values of various types of FTFR in different internal fault positions under grid-connected mode.
Grid-connected mode
Types of fault
Fault position (MW)
side
25%
50%
75%
side
ABG (5 Ω, 5 Ω)
7.52 (0.91)
2.02 (0.80)
0.97 (0.67)
1.83 (0.65)
7.36 (0.60)
ABG (5 Ω, 6 Ω)
6.80 (1.03)
1.28 (0.59)
0.27 (0.15)
1.14 (0.14)
6.22 (0.12)
AB (5 Ω)
1.06 (0.22)
0.89 (0.20)
0.51 (0.17)
0.86 (0.14)
1.05 (0.13)
AG (5 Ω)
4.00 (0.75)
0.78 (0.17)
0.28 (0.12)
0.70 (0.11)
3.86 (0.11)
ABCG (4 Ω, 5 Ω, 6 Ω)
6.34 (1.08)
1.67 (0.42)
0.23 (0.11)
1.45 (0.11)
5.93 (0.10)
ABCG (5 Ω, 5 Ω, 5 Ω)
17.1 (2.84)
6.12 (1.51)
2.05 (1.0)
5.78 (0.09)
16.3 (0.09)