A Novel Protection Scheme against Fault Resistance for AC Microgrid

Table 2

Active power values and the protection threshold setting values of various types of FTFR in different internal fault positions under grid-connected mode.

Grid-connected modeTypes of faultFault position (MW)
side25%50%75% side

ABG (5 Ω, 5 Ω)7.52 (0.91)2.02 (0.80)0.97 (0.67)1.83 (0.65)7.36 (0.60)
ABG (5 Ω, 6 Ω)6.80 (1.03)1.28 (0.59)0.27 (0.15)1.14 (0.14)6.22 (0.12)
AB (5 Ω)1.06 (0.22)0.89 (0.20)0.51 (0.17)0.86 (0.14)1.05 (0.13)
AG (5 Ω)4.00 (0.75)0.78 (0.17)0.28 (0.12)0.70 (0.11)3.86 (0.11)
ABCG (4 Ω, 5 Ω, 6 Ω)6.34 (1.08)1.67 (0.42)0.23 (0.11)1.45 (0.11)5.93 (0.10)

ABCG (5 Ω, 5 Ω, 5 Ω)17.1 (2.84)6.12 (1.51)2.05 (1.0)5.78 (0.09)16.3 (0.09)